Doc. N.° 1SDH000722R0501 - L5942
SACE Tmax XT
Ekip E-LSIG e connettore per conduttore neutro esterno, XT4. Ekip E-LSIG and connector for external neutral conductor, XT4. Ekip E-LSIG und Anschluss für außenliegenden neutralleiter, XT4. Ekip E-LSIG et connecteur pour conducteur neutre extérieur, XT4. Ekip E-LSIG y conectores para conductor neutro externo, XT4.
XT4
1
F-P
W Optional for V Ne Ext
1
-
-
1
JC4
JC4
Ekip E-LSIG
1
F-P
W
1
1
1
XT4
Settaggio di default manuale Manual default setting Manuelle Default-Einstellung Configuration par défauit manuelle Ajuste de default manual
(Neutral setting = OFF) LED
Color
CONDITION Run time
Green
LED Fixed = Device active
L S ELT
Red Red Green
L|S |I
Red
LED Fixed = L pre alarm (0,9 * I1 < I < 1,2 * I1) LED Blinking = L alarm (I > 1,2 * I1) LED Blinking = S alarm (I > I2) LED Fixed = Electronic settings - OFF = Manual settings LED Blinking = Parameters inconsistency - L=I or S >= I. LED Blinking without Parameters inconsistency = generic fault (please contact ABB)
2
XT4
Esempio - Example - Beispiel - Exemple - Ejemplo In = 100A I1 = 100x(0,4+0,04+0,08)=52A t1 = 12s @156A (3I1)
In (A) 0,4 40 16 63 25 XT4 100 40 160 64 250 100
0,44 17,6 27,7 44 70,4 110
0,48 19,2 30,2 48 76,8 120
I1 (In) … 0,92 0,96 1 … 36,8 38,4 40 … 58 60,5 63 … 92 96 100 … 147,2 153,6 160 … 230 240 250
3
XT4
Esempio - Example - Beispiel - Exemple - Ejemplo In = 100A I2 = 100x(3)=300A t2 = 0,2s
In (A) 40 63 XT4 100 160 250
SACE Tmax | ABB
3 120 189 300 480 750
I2(In) 6 9 240 360 378 567 600 900 960 1440 1500 2250
4
XT4
Esempio - Example - Beispiel - Exemple - Ejemplo In = 100A I3 = 100x(1+3)=400A
I3 (In) In (A) 1 3 40 40 120 63 63 189 XT4 100 100 300 160 160 480 250 250 750
4 160 252 400 640 1000
6 240 378 600 960 1500
7 9 10 280 360 400 441 567 630 700 900 1000 1120 1440 1600 1750 2250 2500
5
Trip Test with Ekip TT
1 PROCEDURA DI CONTROLLO - CONTROLLO LED: tutti i led del relè si devono accendere - ULTIMA INDICAZIONE DI TRIP: se presente nella memoria del relè - LED: resta acceso finchè l’unità TT e’ connessa al relè - PRONTO PER TRIP
DIAGNOSTIC PROCEED - UNIT CHECK LED: all the leds in the relay must come on - LAST TRIP INDICATION: if present in the relay's data store - LED: remains on for as long as the TT is connected to the relay - READY TO TRIP
DIAGISTIKABLAUF - EINEITHSPRUF-LED: Alle LEDs des Relais müssen aufleuchten - ANGABE DER LETZTEN AUSLOSUNG: Wenn im Speicher des Relais vorhanden. - LED: Bleibt angeschaltet, bis die Einheit TT an die Relais angeschlossen ist. - AUSLOSEBEREIT
PROCÉDURE DE DIAGNOSTIC - UNIT CHECK LED : toutes les diodes du relais doivent s'allumer - LAST TRIP INDICATION : si présente dans la mémoire du relais - LED: la DIODE reste allumée tant que l'unité TT est connectée au relais - READY TO TRIP
PROCEDIMIENTO DIAGNOSTICO - LED CONTROL UNIDAD: todos los led del relé se deben encender - INDICACION ULTIMA ACTUACION: si está presente en la memoria del relé - LED: queda encendido mientras la unidad TT permanezca conectada con el relé - LISTO PARA LA ACTUACION
LED Ekip TT Verde Green Grün Vert Verde
2
3
TRIP
Rosso Red Rot Rouge Rojo
Dispositivo acceso Sostituire batterie Device ON Change battery Einrichtung eingeschaltet Batterie ersetzen Dispositif allumé Remplacer batteries Dispositivo encendido Sustituir baterías
4 6
CLACK ELT by default setting
EKIP E-LSIG
LED ON = ELT
L S I G UV OV
Trip unit configuration
I1 t1 Curve type I2 t2 I3 I4 t4 U10 t10 U11 t11 Neutral configuration External neutral sensor Nominal Voltage (Un) Electronic/Manual parameters Led Mode
DEFAULT 1 In 60s 2 t=k/I OFF 0.4s 4 In OFF 0.8s OFF 5s OFF 5s 100% OFF 415V MANUAL POWER MODE
Settaggio di default elettronico Electronic default setting Elektronische Standardeinstellung Réglage par défaut électronique Configuración electrónica predeterminada
SACE Tmax | ABB
7
ELT by communication system
LED ON = ELT Esempio - Example - Beispiel - Exemple - Ejemplo USB 2.0
Programmazione e Test con Unità EKIP T&P Programming and test with EKIP T&P Programmierung und Test mit Einheit EKIP T&P Programmation et Test avec Unité EKIP T&P Programación y prueba con Unidad EKIP T&P
EKIP E-LSIG I1 t1 Curve type I2 t2 I3 I4 t4 Neutral configuration Electronic/Manual parameters
L S I G Trip unit configuration
Settaggio tramite sist. di comunicazione Setting by communication system Einstellung über Kommunikationssystem Réglage par syst. de communication Configuración mediante sist. de comunicación
Led Mode
EKIP E-LSIG
DEFAULT ON OFF - 0.5 Un 5s
OV
Trip Status U11 t11
ON/OFF 1.05…1.2 un step 0.01 Un 0.1…5s step 0.1s
ON ON - 1.2 Un 5s
Trip unit configuration
External neutral sensor Nominal Voltage (Un)
OFF/ON 100…690V step 1V
OFF 415V
only with Vaux
ON/OFF 0.5…0.95 Un step 0.01 Un 0.1…5s step 0.1s
Example setting OV-UV on Ekip E-LSIG by communication system
OV
UV
Un = 690 V U10 = 0.75 * Un = 690*0.75 = 517.5 V t10 = 3 s
t11 t10
U11 = 1.1 * Un = 690*1.1 = 759 V t11= 1 s U10
U11 Un
SACE Tmax | ABB
RANGE Trip Status U10 t10
Un = 415 V
U11 = 1.2 * Un = 415*1.2 = 498 V t11= 5 s
DEFAULT 1 In 60s t=k/I2 OFF - 3 In 0.4s ON - 4 In OFF - 1 In 0.8s 100% MANUAL POWER MODE
UV
Default setting OV-UV on Ekip E-LSIG by communication system
U10 = 0.5 * Un = 415*0.5 = 207.5 V t10 = 5 s
RANGE 0.4…1 In step 0.01 In 3…60s step 0.5s t=k/I2; t=k 1…10 In step 0.1 In 0.05…1s step 0.01 1…10 In step 0.1 In 0.2…1 In step 0.02 0.1…0.8s step 0.05s OFF/50%/100% MANUAL/ELECTRONIC POWER MODE (fixed) ALIVE MODE (flash)
U
8
XT4 * PE
N
G)
L1
L2
47
L3 K51 PE
N
L1
L2
L3
JL1 X41
>
T5 4
XV
>>
> Q
TI/L1
>>
TI/L2
>>
>>> >>
TI/L1
>>>
Ekip TI/L2
TI/L3
V1
E-LSIG
>>
S75I/1
XG
TI/L3 V
2
>>
K51
Q
WH TI/N
TI/N
X41
T5
X41
T6
X43
V11
Ekip E-LSIG
V
WH XH4 1
XV
XG
JL1 X41
XH4
T6
63 JC4 X43
9
XT4 F-P V Ne Ext only
V11
10
XT4 F-P V Ne Ext only
3
1
2
1
11
XT4 F-P V Ne Ext only
SACE Tmax | ABB
12
XT4 F-P V Ne Ext only
14
XT4 F-P V Ne Ext only
13
XT4 F-P V Ne Ext only
15
XT4 F-P V Ne Ext only
3 2 1
16
XT4 F-P V Ne Ext only
1
2 2
SACE Tmax | ABB
17
XT4 F-P V Ne Ext only
18
XT4 F-P V Ne Ext only
19
XT4 W V Ne Ext only
1 1,1 Nm
2
2
3 1 3 4
2
1
20
XT4 W V Ne Ext only
21
XT4 W V Ne Ext only
3
2
3 1 1 2
1 1
22
XT4 W V Ne Ext only
23
XT4 W V Ne Ext only
SACE Tmax | ABB
24
XT4 W V Ne Ext only
25
XT4 W V Ne Ext only
1
26
XT4 W V Ne Ext only
3 2 1
4
27
JC4
XT4 W V Ne Ext only
28
XT4 W V Ne Ext only
2 1
1
SACE Tmax | ABB
29
XT4 W V Ne Ext only
30
XT4 W V Ne Ext only
1 1,1 Nm
2
3
3
31
XT4 W V Ne Ext only
32
XT4 W V Ne Ext only
1
2
1 JC4
2
33
XT4 F-P-W V Ne Ext: fixing CABLE on ext. neutral conductor, and setting
A cura del Cliente. Under the Customer's responsibility. À la charge du Client. Vom Kunden beizustellen. A cargo del Cliente.
V11 EKIP E-LSIG Trip unit configuration
External neutral sensor
RANGE
DEFAULT
OFF/ON
OFF
XT4 F-P-W V Ne Ext setting
© Copyright 2011 ABB. All rights reserved.
http://www.abb.com
Set ON