SACE Tmax XT

Color. CONDITION Run time. LED Blinking = S alarm (I > I2). (Neutral setting = OFF). In (A) 0,4 0,44 0,48 … 0,92. 0,96. 1. 40. 16. 17,6 19,2 … 36,8. 38,4. 40. 63.
4MB Größe 14 Downloads 273 vistas
Doc. N.° 1SDH000722R0501 - L5942

SACE Tmax XT

Ekip E-LSIG e connettore per conduttore neutro esterno, XT4. Ekip E-LSIG and connector for external neutral conductor, XT4. Ekip E-LSIG und Anschluss für außenliegenden neutralleiter, XT4. Ekip E-LSIG et connecteur pour conducteur neutre extérieur, XT4. Ekip E-LSIG y conectores para conductor neutro externo, XT4.

XT4

1

F-P

W Optional for V Ne Ext

1

-

-

1

JC4

JC4

Ekip E-LSIG

1

F-P

W

1

1

1

XT4

Settaggio di default manuale Manual default setting Manuelle Default-Einstellung Configuration par défauit manuelle Ajuste de default manual

(Neutral setting = OFF)  LED

 Color

CONDITION  Run time

 Green

LED Fixed = Device active

 L  S ELT

 Red  Red  Green

L|S |I

 Red

LED Fixed = L pre alarm (0,9 * I1 < I < 1,2 * I1) LED Blinking =  L alarm (I > 1,2 * I1) LED Blinking = S alarm (I > I2) LED Fixed = Electronic settings - OFF = Manual settings LED Blinking = Parameters inconsistency - L=I or S >= I. LED Blinking without Parameters inconsistency = generic fault (please contact ABB)

2

XT4

Esempio - Example - Beispiel - Exemple - Ejemplo In = 100A I1 = 100x(0,4+0,04+0,08)=52A t1 = 12s @156A (3I1)

In (A) 0,4 40 16 63 25 XT4 100 40 160 64 250 100

0,44 17,6 27,7 44 70,4 110

0,48 19,2 30,2 48 76,8 120

I1 (In) … 0,92 0,96 1 … 36,8 38,4 40 … 58 60,5 63 … 92 96 100 … 147,2 153,6 160 … 230 240 250

3

XT4

Esempio - Example - Beispiel - Exemple - Ejemplo In = 100A I2 = 100x(3)=300A t2 = 0,2s

In (A) 40 63 XT4 100 160 250

SACE Tmax | ABB

3 120 189 300 480 750

I2(In) 6 9 240 360 378 567 600 900 960 1440 1500 2250

4

XT4

Esempio - Example - Beispiel - Exemple - Ejemplo In = 100A I3 = 100x(1+3)=400A

I3 (In) In (A) 1 3 40 40 120 63 63 189 XT4 100 100 300 160 160 480 250 250 750

4 160 252 400 640 1000

6 240 378 600 960 1500

7 9 10 280 360 400 441 567 630 700 900 1000 1120 1440 1600 1750 2250 2500

5

Trip Test with Ekip TT

1 PROCEDURA DI CONTROLLO - CONTROLLO LED: tutti i led del relè si devono accendere - ULTIMA INDICAZIONE DI TRIP: se presente nella memoria del relè - LED: resta acceso finchè l’unità TT e’ connessa al relè - PRONTO PER TRIP

DIAGNOSTIC PROCEED - UNIT CHECK LED: all the leds in the relay must come on - LAST TRIP INDICATION: if present in the relay's data store - LED: remains on for as long as the TT is connected to the relay - READY TO TRIP

DIAGISTIKABLAUF - EINEITHSPRUF-LED: Alle LEDs des Relais müssen aufleuchten - ANGABE DER LETZTEN AUSLOSUNG: Wenn im Speicher des Relais vorhanden. - LED: Bleibt angeschaltet, bis die Einheit TT an die Relais angeschlossen ist. - AUSLOSEBEREIT

PROCÉDURE DE DIAGNOSTIC - UNIT CHECK LED : toutes les diodes du relais doivent s'allumer - LAST TRIP INDICATION : si présente dans la mémoire du relais - LED: la DIODE reste allumée tant que l'unité TT est connectée au relais - READY TO TRIP

PROCEDIMIENTO DIAGNOSTICO - LED CONTROL UNIDAD: todos los led del relé se deben encender - INDICACION ULTIMA ACTUACION: si está presente en la memoria del relé - LED: queda encendido mientras la unidad TT permanezca conectada con el relé - LISTO PARA LA ACTUACION

LED Ekip TT Verde Green Grün Vert Verde

2

3

TRIP

Rosso Red Rot Rouge Rojo

Dispositivo acceso Sostituire batterie Device ON Change battery Einrichtung eingeschaltet Batterie ersetzen Dispositif allumé Remplacer batteries Dispositivo encendido Sustituir baterías

4 6

CLACK ELT by default setting

EKIP E-LSIG

LED ON = ELT

L S I G UV OV

Trip unit configuration

I1 t1 Curve type I2 t2 I3 I4 t4 U10 t10 U11 t11 Neutral configuration External neutral sensor Nominal Voltage (Un) Electronic/Manual parameters Led Mode

DEFAULT 1 In 60s 2 t=k/I OFF 0.4s 4 In OFF 0.8s OFF 5s OFF 5s 100% OFF 415V MANUAL POWER MODE

Settaggio di default elettronico Electronic default setting Elektronische Standardeinstellung Réglage par défaut électronique Configuración electrónica predeterminada

SACE Tmax | ABB

7

ELT by communication system

LED ON = ELT Esempio - Example - Beispiel - Exemple - Ejemplo USB 2.0

Programmazione e Test con Unità EKIP T&P Programming and test with EKIP T&P Programmierung und Test mit Einheit EKIP T&P Programmation et Test avec Unité EKIP T&P Programación y prueba con Unidad EKIP T&P

EKIP E-LSIG I1 t1 Curve type I2 t2 I3 I4 t4 Neutral configuration Electronic/Manual parameters

L S I G Trip unit configuration

Settaggio tramite sist. di comunicazione Setting by communication system Einstellung über Kommunikationssystem Réglage par syst. de communication Configuración mediante sist. de comunicación

Led Mode

EKIP E-LSIG

DEFAULT ON OFF - 0.5 Un 5s

OV

Trip Status U11 t11

ON/OFF 1.05…1.2 un step 0.01 Un 0.1…5s step 0.1s

ON ON - 1.2 Un 5s

Trip unit configuration

External neutral sensor Nominal Voltage (Un)

OFF/ON 100…690V step 1V

OFF 415V

only with Vaux

ON/OFF 0.5…0.95 Un step 0.01 Un 0.1…5s step 0.1s

Example setting OV-UV on Ekip E-LSIG by communication system

OV

UV

Un = 690 V U10 = 0.75 * Un = 690*0.75 = 517.5 V t10 = 3 s

t11 t10

U11 = 1.1 * Un = 690*1.1 = 759 V t11= 1 s U10

U11 Un

SACE Tmax | ABB

RANGE Trip Status U10 t10

Un = 415 V

U11 = 1.2 * Un = 415*1.2 = 498 V t11= 5 s

DEFAULT 1 In 60s t=k/I2 OFF - 3 In 0.4s ON - 4 In OFF - 1 In 0.8s 100% MANUAL POWER MODE

UV

Default setting OV-UV on Ekip E-LSIG by communication system

U10 = 0.5 * Un = 415*0.5 = 207.5 V t10 = 5 s

RANGE 0.4…1 In step 0.01 In 3…60s step 0.5s t=k/I2; t=k 1…10 In step 0.1 In 0.05…1s step 0.01 1…10 In step 0.1 In 0.2…1 In step 0.02 0.1…0.8s step 0.05s OFF/50%/100% MANUAL/ELECTRONIC POWER MODE (fixed) ALIVE MODE (flash)

U

8

XT4 * PE

N

G)

L1

L2

47

L3 K51 PE

N

L1

L2

L3

JL1 X41

>

T5 4

XV

>>

> Q

TI/L1

>>

TI/L2

>>

>>> >>

TI/L1

>>>

Ekip TI/L2

TI/L3

V1

E-LSIG

>>

S75I/1

XG

TI/L3 V

2

>>

K51

Q

WH TI/N

TI/N

X41

T5

X41

T6

X43

V11

Ekip E-LSIG

V

WH XH4 1

XV

XG

JL1 X41

XH4

T6

63 JC4 X43

9

XT4 F-P V Ne Ext only

V11

10

XT4 F-P V Ne Ext only

3

1

2

1

11

XT4 F-P V Ne Ext only

SACE Tmax | ABB

12

XT4 F-P V Ne Ext only

14

XT4 F-P V Ne Ext only

13

XT4 F-P V Ne Ext only

15

XT4 F-P V Ne Ext only

3 2 1

16

XT4 F-P V Ne Ext only

1

2 2

SACE Tmax | ABB

17

XT4 F-P V Ne Ext only

18

XT4 F-P V Ne Ext only

19

XT4 W V Ne Ext only

1 1,1 Nm

2

2

3 1 3 4

2

1

20

XT4 W V Ne Ext only

21

XT4 W V Ne Ext only

3

2

3 1 1 2

1 1

22

XT4 W V Ne Ext only

23

XT4 W V Ne Ext only

SACE Tmax | ABB

24

XT4 W V Ne Ext only

25

XT4 W V Ne Ext only

1

26

XT4 W V Ne Ext only

3 2 1

4

27

JC4

XT4 W V Ne Ext only

28

XT4 W V Ne Ext only

2 1

1

SACE Tmax | ABB

29

XT4 W V Ne Ext only

30

XT4 W V Ne Ext only

1 1,1 Nm

2

3

3

31

XT4 W V Ne Ext only

32

XT4 W V Ne Ext only

1

2

1 JC4

2

33

XT4 F-P-W V Ne Ext: fixing CABLE on ext. neutral conductor, and setting

A cura del Cliente. Under the Customer's responsibility. À la charge du Client. Vom Kunden beizustellen. A cargo del Cliente.

V11 EKIP E-LSIG Trip unit configuration

External neutral sensor

RANGE

DEFAULT

OFF/ON

OFF

XT4 F-P-W V Ne Ext setting

© Copyright 2011 ABB. All rights reserved.

http://www.abb.com

Set ON