Power Limited Fire Alarm Cable Part No. 4106 - itt ingenieria

Jacket. Type. PVC. Color. Red. Thickness. 0.015" nom. Diameter. 0.134" nom. Legend (Ink Print). HONEYWELL P/N 4106 2C18 E175105 (UL) FPL OR CL2 ...
17KB Größe 14 Downloads 51 vistas
GENESIS SERIES

Power Limited Fire Alarm Cable Part No. 4106

Description: Compliance:

18 AWG 2/C SOL FPL-CL2 UL Standards 13 & 1424; NEC Articles 725 & 760

Construction: Conductor No. of Conductors Assembly

18 AWG Solid Bare Copper 2 Tubed jacket over twisted insulated conductors

Type Color Thickness Diameter Lay Length

Insulation Polypropylene Black, Red 0.006" nom. 0.052" nom. 1.75" nom.

Type Color Thickness Diameter Legend (Ink Print)

Properties: Temperature Rating Operating Voltage Capacitance Impedance DC Resistance Flame Rating

REV A 09/01/10 OA

Jacket PVC Red 0.015" nom. 0.134" nom. HONEYWELL P/N 4106 2C18 E175105 (UL) FPL OR CL2 SUN RES 75C (RoHS) W/O# XXXXXX-XXXXXX XXXXX FT DEVICE/ZONE A B C D E F 1 2 3 4 5 6 7 8 9

-20 to 75 oC 300 Volts max. 20 pf/ft nom. 81 Ohms nom. 6.5 Ohms/M' at 20oC UL 1685 Vertical Tray