PV UL

0.18". Ø. Label that indicates type of jumper kit installed on breaker. MIN 14 AWG. MAX 1/0 AWG. Cu. Stranded. CABLE SECTION: required Cu wires (number x section) ambient T 40°C (UL489). In (A). 50°C (UL489B). 100. 1 x 3 AWG. 1 x 1/0 AWG. 1,1 Nm. 10 lb·in min 16 mm min 0.63". 14 AWG...1/0 AWG = 7 Nm / 62 lb in.
746KB Größe 92 Downloads 13 vistas
Doc. N.° 1SDH000777R0003 - L9260

SACE Tmax T1N-D/PV UL

Connessione per Jumper Tmax T1N-D/PV UL Jumper connection Tmax T1N-D/PV UL

connection A T1N-D/PV-A grounded system wiring 4PS Kit

Upper supply

3

3

1

Lower supply

3

3

1

connection B T1N-D/PV-B ungrounded system wiring 2PS+2PS Kit

Upper supply

1

2

1

2

1

Lower supply

1

2

1

2

1

A

B

X

X

Y

X

X

CLACK

Y

Y

OFF

ON

TRIPPED

55 2.17"

200

Y

7.87"

200 7.87"

1 x 3 AWG (40°C) 1 x 1/0 AWG (50°C)

Busbar Jumper Kit T1N-D/PV-A for connection A grounded system wiring 4PS, lower supply

Busbar Jumper Kit T1N-D/PV-B for connection B ungrounded system wiring 2PS+2PS, lower supply

D

LOAD

LOAD

Connection A 4PS FCCu

Connection B 2PS+2PS FCCu

Availability for Lower supply

2PS+2PS LOWER SUPPLY

14 0.55" 36 1.42"

130 5.12"

25.7 1.01"

4 0.16"

65 2.56"

46.1 1.82"

Y

65 2.56"

4PS LOWER SUPPLY

36 1.42"

4 0.16"

100 3.94"

25.7 1.01"

X

X

130 5.12"

14 0.55" 36 1.42"

Availability for Lower supply

46.1 1.82"

36 1.42"

LOAD

100 3.94"

C

X

X

7Nm

7Nm

62 lb·in

62 lb·in

25 25 25 0.98" 0.98" 38.1 0.98" 1.5" 101.2 3.98"

11.2 0.44"

25 25 25 0.98" 0.98" 0.98" Y 38.1 1.5"

71 2.8" (see fig.H)

50 1.97" 103 4.06"

Connection B 2PS+2PS

Availability for Upper supply* FCCu

4PS UPPER SUPPLY

11.2 0.44" 71 2.8" (see fig.H)

Busbar Jumper Kit T1N-D/PV-B for connection B ungrounded system wiring 2PS+2PS, upper supply

F

Connection A 4PS

Availability for Upper supply*

25 0.98"

101.2 3.98"

103 4.06"

Busbar Jumper Kit T1N-D/PV-A for connection A grounded system wiring 4PS, upper supply

E

1 0.04"

100 3.94"

1 0.04" 25 0.98"

FCCu

LOAD

LOAD

LOAD

2PS+2PS UPPER SUPPLY

* Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from the top.

G Le uniche configurazioni utilizzabili sono quelle riportate in questo documento The configurations here represented are the only ones available

Tmax T1N-D/PV UL| ABB

H 12.5 0.49"

Ø 4.5 (M4) Ø 0.18"

A WITHOUT FLANGE SENZA MOSTRINA (mm)

53.5 2.11"

Y

B

C

D

E

80

78.2

47

18

39.1

72

103.2

47

18

39.1

3.08"

1.85"

0.71"

1.54"

103.2

1.85"

0.71"

1.54"

WITHOUT FLANGE 3,14" SENZA MOSTRINA 2.83" (inch)

X

107 4.21"

X B E

Y

50 1.97"

X

D

12.5 0.49"

C

Y

X Y A

min 16 mm min 0.63"

I 14 AWG...1/0 AWG = 7 Nm / 62 lb in

Cu Stranded

1,1 Nm 10 lb·in

MIN 14 AWG MAX 1/0 AWG CABLE SECTION:

required Cu wires (number x section)

ambient T 40°C (UL489) In (A) 1 x 3 AWG 100

Jumper example

Label that indicates type of jumper kit installed on breaker 7 Nm 62 lb·in

www.abb.com © Copyright 2011-2014 ABB. All rights reserved.

50°C (UL489B) 1 x 1/0 AWG