POTENTIAL TRANSFORMER 3.6 kV – 38 kV FUSES
These are a range of fuses with low current rating, for use with voltage transformers or operating transformers to provide isolation of the associated system in the event of faults in the transformer circuit. Advantages of Edison P.T. Fuses Most fuses have two elements in parallel, ensuring satisfactory operation at much smaller values of overcurrent than is possible with single element fuse.
Application Notes 1. In order to minimize the risk of deterioration of the fine fuse elements caused by corona, it is desirable to mount the fuses so that grounded metal is not in the immediate vicinity of the part of the barrel between the ferrules. 2. It is recommended that all three fuses are replaced when the fuse in one or two phases has operated unless it is definitely known that no overcurrent has passed through the unmelted fuses.
The elements are wound on a ceramic former, thus ensuring correct spacing of the elements from the body wall and from each other and hence giving assurance of correct operation in service. Switching (arc) voltages comply with the IEC282-1.
“AB” & “AM” Series Catalog kV Number 3.6 3.6ABWNA(amp) 3.6 3.6ABCNA(amp) 5.5 5.5ABWNA(amp) 5.5 5.5AMWNA(amp) 7.2 7.2ABWNA(amp) 7.2 7.2ABCNA(amp) 12.0 12ABCNA(amp) 15.5 15.5ABFNA(amp) 17.5 17.5ABGNA(amp) 24.0 24ABGNA(amp) 36.0* 36ABGNA(amp) *For clean indoor applications only.
Ampere Ratings 3.15, 6.3 3.15, 6.3, 10 0.5E, 1.0E, 2.0E, 3.0E, 5.0E 0.5E, 1.0E, 2.0E, 3.0E, 5.0E 3.15, 6.3 3.15, 6.3 3.15 3.15 3.15 3.15 3.15
Type AB AB AB AM AB AB AB AB AB AB AB
Dimensions (Figure 1) Length Diameter 5.6” 1” 7.69” 1” 5.6” 1” 5.6” .81” 5.6” 1” 7.69” 1” 7.69” 1” 10.00” 1” 14.13” 1” 14.13” 1” 14.13” 1”
Ampere Ratings 2 15E 0.5E, 1E, 2E 2, 10 2 0.5E, 1E, 2E, 3E, 7E 0.5E, 1E, 2E 2, 4, 6, 10 2, 3, 4 2, 4 4E 0.5E, 1E, 2E
Type 8CAV 7CAV 7CAVH 8CAV 8CAV 12CAV 12CAVH 8CAV 13CAV 17CAV 17CAV 17CAV
Dimensions (Figure 2) Length Diameter 8.66” 7.375” 7.375” 8.66” 8.66” 12.87” 1.63” 12.87” 8.66” 13.39” 17.32” 17.32” 17.32”
IR
50KA
“CAV” Series kV 3.6 5.5 5.5 7.2 12 15.5 15.5 17.5 24 36 38 38
Catalog Number 3.6CAV(amp) 5.5CAV(amp) 5.5CAVH(amp) 7.2CAV(amp) 12CAV(amp) 15.5CAV(amp) 15.5CAVH(amp) 17.5CAV(amp) 24CAV(amp) 36CAV(amp) 38CAV(amp) 38CAVH(amp)
IR
40KA
129
POTENTIAL TRANSFORMER 3.6 kV – 38 kV FUSES .21" .5" 12.7mm 5.3mmø
Dimensions (Type AB & AM)
1" 25.4mm
0.63" (15.9mm) FOR AMWNA 1.26" (32.1mm) FOR ALL OTHERS
FOR LENGTH SEE TABLE
.34" 8.6mm
.68" 17.3mm
FOR DIAMETER SEE TABLE
Figure 1 1.37" 34.8mm
Dimensions (Type CAV)
FOR DIAMETER SEE TABLE
Ref. No. A3354705 For 1” diameter potential transformer fuses.
1.18" 30.20mm FOR LENGTH SEE TABLE
Figure 2
Time/Current-Curves
.1
100
RMS SYMMETRICAL CURRENT IN AMPERES
1,000
RMS SYMMETRICAL CURRENT IN AMPERES
1,000
.01 100
.01 10
.1
1
.1
.1
2.0 3.0
1
10
1
10
1
TIME IN SECONDS
10
130
"E" RATING
100
100
TIME IN SECONDS
1,000
1.0
"E" RATING
0.5
(5.5kV ABWNA & 15.5kV CAV) 2.0 3.0 4.0 5.0
1.0
1,000
0.5
(5.5kV AMWNA)
Mouser Electronics Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Cooper Bussmann: 12ABCNA3.15 15.5CAV5E 17.5ABGNA3.15 17.5CAV2 17.5CAV6 24ABGNA3.15 24CAV2 24CAV3 24OBGNA3.15 3.6ABCNA3.15 3.6ABWNA3.15 3.6ABWNA6.3 36CAV2 3.6CAV2 36CAV4 38CAV4E 38CAVH0.5E 38CAVH1E 38CAVH2E 5.5CAV15E 5.5CAVH0.5E 5.5CAVH1E 5.5CAVH2E 24OBGNA3.15UK 17.5CAV4 36ABGNA3.15 7.2ABCNA6.3 3.6ABCNA10 36ABGN223.15 5.5ABWNA2E 15-5ABFNA3-15 5.5ABWNA3E 7.2ABWNA3.15 5.5ABWNA0.5E 3.6ABCNA6.3 7.2ABWNA6.3 5.5ABWNA5E 7.2ABCNA3.15 5.5ABWNA1E 15.5ABFNA3.15