NQ/NQM Panelboards and QONQ Load Centers Information Manual
Para los tableros de alumbrado NQ/NQM y centros de carga QONQ Boletín de instrucciones
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Directives d’utilisation Instruction Bulletin Boletín de instrucciones Directives d’utilisation 80043-712-06 Rev. 02 11/2016 Retain for future use. / Conservar para uso futuro. / À conserver pour usage ultérieur.
™
ENGLISH
NQ/NQM Panelboards and QONQ Load Centers Information Manual Class 1640
Instruction Bulletin 80043-712-06 Rev. 02 11/2016 Retain for future use.
™
ENGLISH
Hazard Categories and Special Symbols
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.
CAUTION CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.
NOTICE NOTICE is used to address practices not related to physical injury. The safety alert symbol is not used with this signal word. NOTE: Provides additional information to clarify or simplify a procedure.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
80043-712-06 Rev. 02 11/2016
NQ/NQM Panelboards and QONQ Load Centers Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Interior Mounting for Square D Brand Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . 6 Surface Mounting (Enclosure Mounted on Wall) . . . . . . . . . . . . . . . . . . . . . . . . 7 Flush Mounting (Enclosure Recessed in Wall) . . . . . . . . . . . . . . . . . . . . . . . . . 7 Neutral Bonding Strap/Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 100 or 250 A Maximum NQ Panelboards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 400 or 600 A Maximum NQ Panelboards and QONQ Load Centers . . . . . . . 11 QO and QOB Circuit Breaker Installation and Removal . . . . . . . . . . . . . . . . . . . . 13 QO and QOB Breaker Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 QO and QOB Breaker Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Circuit Breaker Reset Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Interior Trim Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Appendix 1: Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Typical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Integral Main or Sub-Feed: DJ, FI, KI, H, J, LA, LC, LH, QB, QD, QG, QJ, QO(B)VH . . . . . . . . . . . . . . . . 19 Panelboard Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 CE Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Appendix 2: Accessory Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Equipment Ground Bar Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Oversized Lug Kits for 100–250 A Panelboards . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Sub-Feed Lug Kits for 100–400 A Panelboards . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Main Lug Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3
ENGLISH
Table of Contents
NQ/NQM Panelboards and QONQ Load Centers Table of Contents
80043-712-06 Rev. 02 11/2016
List of Tables ENGLISH
Table 1: Table 2: Table 3: Table 4: Table 5: Table 6: Table 7: Table 8: Table 9: Table 10: Table 11:
Panelboard Typical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Series Connected Breaker Ratings (RMS Symmetrical) . . . . . . . . . . . . 23 NQ Panel Mission Critical Breaker Selectivity . . . . . . . . . . . . . . . . . . . . 38 Short Circuit Current Rating for Main Lug Interiors with Sub-Feed or Feed-Through Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Equipment Ground Bar Kits Specifications . . . . . . . . . . . . . . . . . . . . . . 40 Oversized Lug Kits for 100–250 A Panelboards Specifications . . . . . . . 41 Sub-Feed Lug Kits for 100–400 A Panelboards Specifications . . . . . . . 41 Mechanical Lug Kits — Aluminum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Mechanical Lug Kits — Copper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Versa-Crimp® Compression Lug Kits — Aluminum. . . . . . . . . . . . . . . . 42 Versa-Crimp® Compression Lug Kits — Copper . . . . . . . . . . . . . . . . . . 43
List of Figures Figure 1: Figure 2: Figure 3: Figure 4: Figure 5: Figure 6: Figure 7: Figure 8: Figure 9: Figure 10:
4
Interior Mounting of Square D Brand Enclosures . . . . . . . . . . . . . . . . . . . 8 Bonding Strap Installation — 100 or 250 A Maximum NQ Panelboards. . . . . . . . . . . . . . . . . . . . . . . . 11 Bonding Cable Installation — 400 or 600 A Maximum NQ Panelboards and QONQ Load Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 QO and QOB Circuit Breaker Installation and Removal. . . . . . . . . . . . . 15 Circuit Breaker Handle Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Interior Trim Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 NQ/NQM 100–225 A Main Lugs or 100–250 A Main Breaker Diagram . 19 NQ Panelboard or QONQ Load Center 400–600 A Main Lugs or Main Circuit Breaker with or without Feed-Through Lugs Diagram. . . . . . . . . 20 NQ Panelboard or QONQ Load Center 400–600 A Main Circuit Breaker with Feed-Through Lugs or Sub-Feed Circuit Breakers Diagram . . . . . 21 Typical NQ Panelboard with Split Bus Diagram . . . . . . . . . . . . . . . . . . . 22
80043-712-06_A5Main_eng.fm Page 5 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
NQ/NQM Panelboards and QONQ Load Centers Introduction, Safety Precautions
This bulletin contains instructions for installing Square D™ brand NQ circuit breaker panelboards and QONQ load centers. These panelboards and load centers are Underwriters Laboratories (cULus) listed and accept QO™ and QOB branch circuit breakers. For technical support on the installation of this panelboard, contact the Schneider Electric Customer Information Center at 1-888-778-2733. See the labels on the equipment for rating and safety information. Additional equipment labels are provided with this document.
Safety Precautions
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462, or NOM-029-STPS. • This equipment must only be installed and serviced by qualified electrical personnel. • Turn OFF all power supplying this equipment before working on or inside the equipment. • Always use a properly rated voltage sensing device to confirm all power is OFF. • Read and understand this entire instruction bulletin and the included NEMA PB 1.1 standards publication before installing, operating, or maintaining this equipment. • Local codes vary, but are adopted and enforced to promote safe electrical installations. A permit may be needed to do electrical work, and some codes may require an inspection of the electrical work. • Replace all devices, doors, and covers before turning ON power to this equipment. Failure to follow these instructions will result in death or serious injury.
5
ENGLISH
Introduction
80043-712-06_A5Main_eng.fm Page 6 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Installation
80043-712-06 Rev. 02 11/2016
Installation ENGLISH
This section provides instructions for the following NQ panelboard and QONQ load center procedures:
• • •
“Interior Mounting for Square D Brand Enclosures” on page 6
• •
“Circuit Breaker Reset Instructions” on page 16
“Neutral Bonding Strap/Cable Installation” on page 9 “QO and QOB Circuit Breaker Installation and Removal” on page 13 “Interior Trim Preparation” on page 17
Interior Mounting for Square D Brand Enclosures A separate standards publication, titled “General Instructions for Proper Installation, Operation, and Maintenance of Panelboards Rated 600 Volts or Less” (NEMA PB1.1), has been provided with this equipment. Familiarize yourself with the content of this document before proceeding with any of the following procedures. If you did not receive a copy of this document, or if you have any questions regarding this equipment, contact your local distributor or Schneider Electric representative.
NOTICE HAZARD OF EQUIPMENT DAMAGE DUE TO LOOSE CONNECTIONS • Ensure all connections are properly tightened. • Refer to the torque information label provided on the panelboard before tightening the connections. Failure to follow these instructions can result in equipment damage. To properly mount and install the NQ panelboard or QONQ load center interior, please refer to the NEMA PB 1.1 standards publication, and follow the instructions below for either ““Surface Mounting (Enclosure Mounted on Wall)” on page 7” or ““Flush Mounting (Enclosure Recessed in Wall)” on page 7.”
6
80043-712-06_A5Main_eng.fm Page 7 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
NQ/NQM Panelboards and QONQ Load Centers Installation
ENGLISH
Surface Mounting (Enclosure Mounted on Wall) 1. Mount the enclosure as instructed in the NEMA PB 1.1 standards publication. 2. Remove the interior trim from the trim brackets. 3. Install the interior as described below: a. Set the interior on the enclosure studs. An elevating screw is not required (See Figure 1 on page 8). b. Tighten the Keps nuts against the interior side rails until the rails are against the back of the enclosure. c. Remount the interior trim after wiring. 4. If used as service entrance equipment, neutral bonding is required. See the “Neutral Bonding Strap/Cable Installation” instructions on page 9. 5. Apply equipment labels (located in the bag assembly) as directed by the instructions on the back of the equipment label sheet.
Flush Mounting (Enclosure Recessed in Wall) 1. Mount the enclosure as instructed in the NEMA PB 1.1 standards publication. 2. Remove the interior trim from the trim brackets. 3. Install the interior as described below: a. Thread the (4) 10-32 x 0.875 in. self-tapping, elevating screws provided with the flush trim into the side rails. b. Set the interior on the enclosure studs (see Figure 1 on page 8). Place the keps nuts onto the enclosure studs, but do not tighten. c. Adjust the screws so that the lip of the interior trim is approximately 0.25 inches (6.35 mm) from the wall line. d. Tighten the keps nuts against the side rails. e. Remount the interior trim after wiring. 4. If used as service entrance equipment, neutral bonding is required. See the “Neutral Bonding Strap/Cable Installation” instructions on page 9. 5. Apply equipment labels (located in the bag assembly) as directed by the instructions on the back of the equipment label sheet.
7
80043-712-06_A5Main_eng.fm Page 8 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Installation
Figure 1:
80043-712-06 Rev. 02 11/2016
Interior Mounting of Square D Brand Enclosures
ENGLISH
Interior Trim
0.25 in. (6.35 mm)
Wall
Trim Bracket
Elevating Screw Enclosure Stud
Keps Nut Enclosure
8
Side Rail
80043-712-06_A5Main_eng.fm Page 9 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
NQ/NQM Panelboards and QONQ Load Centers Installation
The neutral bonding strap/cable should be used only when the panelboard is installed as service entrance equipment. To properly bond the neutral to the panelboard, follow the instructions for either “100 or 250 A Maximum NQ Panelboards” or “400 or 600 A Maximum NQ Panelboards and QONQ Load Centers” below and on page 11, respectively.
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462, or NOM-029-STPS. • Turn OFF all power supplying this equipment before working on or inside the equipment. • The main bonding strap/cable should be used only when the panelboard is installed as service entrance equipment. • Do not mix the mounting screws with the interior trim screws. Failure to follow these instructions will result in death or serious injury.
NOTE: The bonding strap/cable parts are found in the bag assembly provided with the interior. 100 or 250 A Maximum NQ Panelboards To install a neutral bonding strap on a 100 or 250 A maximum NQ panelboard, refer to Figure 2 and follow the instructions below. 1. Align the bonding strap on the side rail, as pictured. NOTE: For some applications, it may be necessary to remove the lug (not pictured) before installing the bonding strap.
9
ENGLISH
Neutral Bonding Strap/Cable Installation
80043-712-06_A5Main_eng.fm Page 10 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Installation
80043-712-06 Rev. 02 11/2016
ENGLISH
2. Insert the two mounting screws, as pictured. Tighten the 10-32 screw to 10–12 lb-in (1.1–1.4 N•m) and the 1/4-20 to 25–30 lb-in (2.8–3.4 N•m). NOTE: If the lug was removed in Step 1 above, reinstall it on top of the bonding strap. Use the 1/4-20 screw x 11/16 in. lug mounting screw on applications with feed-through lug, sub-feed lug, sub-feed breaker, or 200% neutral applications. Use the 1/420 screw x 7/8 in lug mounting screw on 225 A applications with 200% neutrals and with feed-thru lugs, sub-feed lugs, or sub-feed circuit breakers. Lug mounting screws are provided in the bonding strap bag assembly.
10
80043-712-06_A5Main_eng.fm Page 11 Monday, January 23, 2017 1:44 PM
Figure 2:
NQ/NQM Panelboards and QONQ Load Centers Installation
Bonding Strap Installation — 100 or 250 A Maximum NQ Panelboards
ENGLISH
80043-712-06 Rev. 02 11/2016
1/4-20 x 9/16 in.
Mounting Screws
Bonding Strap
10-32 x 5/16 in.
Neutral Bus Side Rail
400 or 600 A Maximum NQ Panelboards and QONQ Load Centers To install a neutral bonding cable on a 400 or 600 A maximum NQ panelboard and QONQ load center, refer to Figure 3 and follow the instructions below. 1. Align the lug on the side rail mounting hole, as pictured. 2. Tighten the lug mounting screw against the side rail to 10–12 lb-in (1.1–1.4 N•m).
11
80043-712-06_A5Main_eng.fm Page 12 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Installation
80043-712-06 Rev. 02 11/2016
ENGLISH
3. Align the bonding cable, as pictured, and insert it into the lug and neutral mounting holes. 4. Tighten both the lug wire binding screw and the neutral wire binding screw to 45–50 lb-in (5.1–5.6 N•m). Figure 3:
Bonding Cable Installation — 400 or 600 A Maximum NQ Panelboards and QONQ Load Centers
Neutral Neutral Wire Binding Screw
Lug Wire Binding Screw Lug Lug Mounting Screw
Bonding Cable Bonding Cable Mounting Hole
Side Rail Mounting Hole Side Rail
12
Bonding Cable Mounting Hole
80043-712-06_A5Main_eng.fm Page 13 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
NQ/NQM Panelboards and QONQ Load Centers Installation
ENGLISH
QO and QOB Circuit Breaker Installation and Removal
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462, or NOM-029-STPS. • This equipment must only be installed and serviced by qualified electrical personnel. • Turn OFF all power supplying this equipment before working on or inside equipment. • Always use a properly rated voltage sensing device to confirm that all power is OFF. • All unused spaces must be filled with blank fillers. • Replace all devices, doors, and covers before turning ON power to this equipment. Failure to follow these instructions will result in death or serious injury.
13
80043-712-06_A5Main_eng.fm Page 14 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Installation
80043-712-06 Rev. 02 11/2016
QO and QOB Breaker Installation ENGLISH
Refer to Figure 4 on page 15 for the following instructions: 1. Turn OFF all power to the panelboard. 2. Turn the breaker OFF. 3. Remove the interior trim. 4. Snap the wire terminal end of the circuit breaker onto the mounting rail. 5. Engage the branch connector. For QO Circuit Breakers: a. Push inward until the plug-on jaws fully engage the branch connector. For QOB Circuit Breakers: a. Push inward until the breaker connector is centered on the branch connector mounting hole. Engage the screw into the branch connector hole and tighten it to the torque values shown on the interior wiring and torque diagram. 6. Install the load wire. 7. Reinstall the interior trim. QO and QOB Breaker Removal Refer to Figure 4 on page 15 for the following instructions: 1. Turn OFF all power to the panelboard. 2. Remove the interior trim. 3. Remove the load wire. 4. Disengage the branch connector. For QO Circuit Breakers: a. Pull outward until the plug-on jaws fully disengage the branch connector. For QOB Circuit Breakers: a. Loosen the screw in the breaker connector and pull the breaker off of the branch connector.
14
80043-712-06_A5Main_eng.fm Page 15 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
NQ/NQM Panelboards and QONQ Load Centers Installation
ENGLISH
5. Snap the wire terminal end of the circuit breaker off of the mounting rail. 6. Reinstall the interior trim. Figure 4:
QO and QOB Circuit Breaker Installation and Removal
Wire Terminal
QO Plug-On Jaw
Rail Branch Connector
Wire Terminal
QOB
CL Bolt-On Connector Screw
Rail Branch Connector
15
80043-712-06_A5Main_eng.fm Page 16 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Installation
80043-712-06 Rev. 02 11/2016
Circuit Breaker Reset Instructions ENGLISH
If the circuit breaker is tripped, the handle will be at the mid-position between ON and OFF. To reset the circuit breaker, push the handle to the OFF position, then to the ON position. Figure 5:
Circuit Breaker Handle Positions ON
OFF
Tripped
ON
ON
ON
Handle
OFF
16
OFF
OFF
80043-712-06_A5Main_eng.fm Page 17 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
NQ/NQM Panelboards and QONQ Load Centers Installation
ENGLISH
Interior Trim Preparation
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462, or NOM-029-STPS. • Before energizing the panelboard, all unused spaces must be filled with blank fillers. • Replace all devices, doors, and covers before energizing this equipment. Failure to follow these instructions will result in death or serious injury.
Figure 6:
Interior Trim Diagram
Blank Fillers Interior Trim
NOTE: The back of the interior trim lists the catalog number for its corresponding compatible blank fillers.
17
80043-712-06_A5Main_eng.fm Page 18 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
80043-712-06 Rev. 02 11/2016
Appendix 1: Specifications ENGLISH
Typical Wiring Table 1:
Panelboard Typical Wiring1 1-Phase Panelboards
Voltage AC
18
3-Phase Panelboards
Phase
Wires
Phase
208Y/120
—
—
3
Wires 4
120/240
1
3
—
—
2402
1
2
3
3
2403
1
3
—
—
240/1204
—
—
3
4 Delta
1
Additional information is provided on the panelboard. See the main circuit breaker rating, if used.
2
For this system, the neutral is not used and only circuit breakers rated 240 V AC minimum should be used. Do not use circuit breakers rated 120 V or 120/240 V AC.
3
For a grounded “B” phase system, only circuit breakers rated 240 V AC minimum should be used. Do not use circuit breakers rated 120 V or 120/240 V AC.
4
When wiring for a delta system, phases “A” and “C” must be 120 V to neutral, phase “B” 208 V to neutral. Connect only circuit breakers rated 240 V AC minimum. Do not use circuit breakers rated 120 V or 120/240 V to “B” phase.
80043-712-06_A5Main_eng.fm Page 19 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
Integral Main or Sub-Feed: DJ, FI, KI, H, J, LA, LC, LH, QB, QD, QG, QJ, QO(B)VH Figure 7:
NQ/NQM 100–225 A Main Lugs or 100–250 A Main Breaker Diagram
Isolated Ground
Backfed Main Circuit Breaker
(when installed)
(must be bolt-on, if used)
Ground (when required)
Enclosure Bonding (when required)
Neutral
Integral Main Circuit Breaker (when installed)
19
ENGLISH
80043-712-06 Rev. 02 11/2016
80043-712-06_A5Main_eng.fm Page 20 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
Figure 8:
80043-712-06 Rev. 02 11/2016
ENGLISH
NQ Panelboard or QONQ Load Center 400–600 A Main Lugs or Main Circuit Breaker with or without Feed-Through Lugs Diagram
Load Feed-Through Lugs (when installed)
Ground (when required)
Enclosure Bonding (when required)
Integral Main Circuit Breaker (when installed)
20
Neutral
80043-712-06_A5Main_eng.fm Page 21 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
NQ Panelboard or QONQ Load Center 400–600 A Main Circuit Breaker with Feed-Through Lugs or Sub-Feed Circuit Breakers Diagram
ENGLISH
Figure 9:
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
Subfeed Circuit Breaker(s) (when installed)
Load
Ground (when required)
Enclosure Bonding
Neutral
(when required)
Line Integral Main Circuit Breaker (when installed)
21
80043-712-06_A5Main_eng.fm Page 22 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
Figure 10:
80043-712-06 Rev. 02 11/2016
Typical NQ Panelboard with Split Bus Diagram
ENGLISH
Ground (when required)
Enclosure Bonding (when required)
Integral Main Circuit Breaker (when installed)
22
Neutral
80043-712-06_A5Main_eng.fm Page 23 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
ENGLISH
Panelboard Ratings Refer to NEC section 110-22 and CEC rule 14-014 for more information. The series rated system label is located in the bag assembly. Table 2: Max. System Voltage AC 1, 2
Series Connected Breaker Ratings (RMS Symmetrical) Max. Short Circuit Current Rating
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
22,000
MG
25,000
120/2407 1P/3W
LD, HD, JD
HG, JG
65,000
LG
LJ
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6 Type
1 Pole
2 Pole
3 Pole
QO (B)
15–30 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
—
QO (B) PL
15–30 A
15–60 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
—
QO (B) PL
15–30 A
15–60 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B) GFI
15–30 A
40–60 A
—
QO (B) EPD
15–30 A
40–60 A
—
Continued on next page
23
80043-712-06_A5Main_eng.fm Page 24 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
Table 2: ENGLISH
Max. System Voltage AC 1, 2
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
HJ, JJ
LJ
120/2407 1P/3W
80043-712-06 Rev. 02 11/2016
100,000
DJ 400 A
QJ
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6 Type
1 Pole
2 Pole
3 Pole —
QO (B)
15–70 A
15–125 A
QO (B) VH
15–70 A
15–125 A
—
QO (B) PL
15–30 A
15–60 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
—
QO (B) H
—
15–100 A
— —
QO (B) GFI
—
15–30 A
QO (B) EPD
—
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
—
150 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) AS
15–30 A
15–30 A
—
QO (B) VH
—
150 A
— —
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
Continued on next page
24
80043-712-06_A5Main_eng.fm Page 25 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
Max. System Voltage AC 1, 2
120/2407 1P/3W
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
125,000
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
HL, JL
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6 Type
1 Pole
2 Pole
3 Pole —
QO (B)
15–70 A
15–125 A
QO (B) VH
15–70 A
15–125 A
—
QO (B) PL
15–30 A
15–60 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–30 A
15–30 A
15–30 A
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–30 A
15–125 A
15–150 A
LA/LH (L) 34200MC
18,000
LA/LH (L) 34225MC LA/LH (L) 34250MC LA/LH (L) 34400MC
208Y/120 3P/4W
25,000
LD
DJ-W 150 A MC8 30,000 DJ-W 250 A MC8
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–100 A
—
QO (B) VH
—
15–125 A
15–150 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B)
15–70 A
15–100 A
—
QO (B) VH
—
—
15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
Continued on next page
25
ENGLISH
Table 2:
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
80043-712-06_A5Main_eng.fm Page 26 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
Table 2: ENGLISH
Max. System Voltage AC 1, 2
80043-712-06 Rev. 02 11/2016
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
30,000
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
DJ-W 600 A MC8
LG
65,000 208Y/120 3P/4W LJ
LL
100,000
DJ 400 A
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6 Type
1 Pole
2 Pole
3 Pole
QO (B)
15–70 A
15–100 A
—
QO (B) VH
—
—
15–150 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B) GFI
—
—
15–30 A
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B)
15–70 A
15–125 A
—
QO (B) VH
—
—
15–150 A —
QO (B) GFI
15–30 A
15–60 A
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Continued on next page
26
80043-712-06_A5Main_eng.fm Page 27 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
Max. System Voltage AC 1, 2
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
QJ
208Y/120 3P/4W
100,000
LJ
240/120 3P/4W
22,000
QO (B) VH
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6 Type
1 Pole
2 Pole
3 Pole
QO (B)
15–70 A
15–125 A
15–30 A
QO (B) VH
—
—
15–150 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
15–30 A
15–60 A
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
—
15–30 A
—
QO (B) EPD
—
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) PL
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Continued on next page
27
ENGLISH
Table 2:
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
80043-712-06_A5Main_eng.fm Page 28 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
Table 2: ENGLISH
Max. System Voltage AC 1, 2
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
QD
ED, FD 240/120 3P/4W
80043-712-06 Rev. 02 11/2016
25,000
KD
HD, JD
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6 Type
1 Pole
2 Pole
3 Pole
QO (B)
15–70 A
15–125 A
15–30 A
QO (B) VH
—
—
35–150 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A 15–30 A
QO (B) AS
15–30 A
15–30 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Continued on next page
28
80043-712-06_A5Main_eng.fm Page 29 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
Max. System Voltage AC 1, 2
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
25,000
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
LD
LA, MA
LC 400 A
240/120 3P/4W 42,000
LC 600 A
MG
65,000
LC 400 A
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6 Type
1 Pole
2 Pole
3 Pole
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–30 A
15–125 A
15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Q2L-H
—
100–225 A 100–225 A
QDL
—
70–225 A
QO (B)
15–70 A
15–70 A
70–225 A —
QO (B) VH
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B) VH
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B) VH
15–30 A
15–30 A
15–30 A
QO (B)
15–30 A
15–30 A
—
QO (B) VH
15–30 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Continued on next page
29
ENGLISH
Table 2:
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
80043-712-06_A5Main_eng.fm Page 30 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
Table 2: ENGLISH
Max. System Voltage AC 1, 2
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
LC 600 A
DJ 400 A
DJ_W
240/120 3P/4W
80043-712-06 Rev. 02 11/2016
65,000 DJ, DG, DL 150–600 A
EG, FG, KG
QG
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6 Type
1 Pole
2 Pole
3 Pole
QO (B) VH
15–30 A
15–125 A
15–150 A
QO (B) GFI
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
—
—
15–150 A
QO (B) H
—
15–100 A
—
QO (B)
15–70 A
15–150 A
—
QO (B)-VH
—
QO (B) GFI
15–30 A
110–125 A 15–150 A 15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B) EPD
—
—
15–30 A 15–100 A
QO (B)
15–70 A
15–125 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–30 A
QO (B) VH
—
—
35–150 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) PL
15–30 A
15–60 A
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Continued on next page
30
80043-712-06_A5Main_eng.fm Page 31 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
Max. System Voltage AC 1, 2
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
HG, JG
Type
1 Pole
2 Pole
3 Pole
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
FC_ or KC_22___
QO (B)
15–70 A
15–100 A
15–100 A
FC_ or KC_34___
QO (B) AS
15–30 A
15–30 A
15–30 A
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
15–150 A
65,000 240/120 3P/4W LG
LJ
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) GFI
15–30 A
40–60 A
—
QO (B) EPD
15–30 A
40–60 A
15–30 A 15–30 A
QO (B) EPE
—
—
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
FC_ or KC_22___
QO (B) GFI
15–30 A
15–30 A
—
FC_ or KC_34___
QO (B) AFI
15–20 A
—
—
LL
100,000
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6
Continued on next page
31
ENGLISH
Table 2:
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
80043-712-06_A5Main_eng.fm Page 32 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
Table 2: ENGLISH
Max. System Voltage AC 1, 2
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
DJ 400 A
EJ
240/120 3P/4W
80043-712-06 Rev. 02 11/2016
100,000
LJ
HJ, JJ
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6 Type
1 Pole
2 Pole
3 Pole —
QO (B)
15–70 A
15–125 A
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
15–150 A —
QO (B) GFI
15–30 A
15–60 A
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
—
15–30 A
—
QO (B) EPD
—
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
— 15–100 A
QO (B)
15–70 A
15–125 A
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
35–150 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Continued on next page
32
80043-712-06_A5Main_eng.fm Page 33 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
Max. System Voltage AC 1, 2
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
125,000
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
HL, JL
240/120 3P/4W
200,000
22,000
FI, KI, HR, JR
QO (B) VH Q2-H
QD 240 3P/3W or 240 1P/2W (two pole only) 25,000 ED, FD KD
HD, JD
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6 Type
1 Pole
2 Pole
3 Pole 15–100 A
QO (B)
15–70 A
15–125 A
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
35–150 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
—
—
15–100 A 15–50 A
QO (B) GFI
—
—
QO (B) PL
—
15–30 A
—
QO (B)
—
—
15–30 A
QO (B)
—
—
15–30 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QO (B) PL
—
15–60 A
15–30 A
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) GFI
—
—
15–50 A
QO (B)
—
—
15–100 A
QO (B) GFI
—
—
15–50 A
QO (B)
—
—
15–100 A
QO (B)
—
—
15–100 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
—
—
15–50 A
Continued on next page
33
ENGLISH
Table 2:
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
80043-712-06_A5Main_eng.fm Page 34 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
Table 2: ENGLISH
Max. System Voltage AC 1, 2
80043-712-06 Rev. 02 11/2016
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
25,000
LD
42,000
Type
1 Pole
2 Pole
3 Pole 15–150 A
QO (B) VH
—
—
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
LA, MA
QDL
—
70–225 A
70–225 A
LC 400 A
QO (B) VH
—
—
15–100 A
LC 600 A
QO (B) VH
—
—
15–100 A
MG
QO (B) VH
—
—
150 A
LC 400 A
QO (B) VH
—
—
15–100 A
LC 600 A
QO (B) VH
—
—
15–30 A
QO (B) VH
—
—
15–150 A
DJ 400 A DJ, DG, DL 150–600 A EG, FG, KG 240 3P/3W or 240 1P/2W (two pole only)
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6
QO (B) H
—
15–100 A
—
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B)
—
—
15–100 A
QO (B) GFI
—
—
15–50 A
QO (B)
—
—
15–30 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QG, HG, JG
QO (B) PL
—
—
15–30 A
QO (B)
—
—
15–100 A
HG, JG
QO (B) VH
—
—
35–150 A
QG
65,000
QO (B) H
—
15–100 A
—
FC_ or KC_22___
QO (B)
—
—
15–100 A
FC_ or KC_34___
QO (B) AS
—
15–30 A
15–30 A
QO (B) VH
—
—
15–150 A
QO (B) H
—
15–100 A
—
QO (B) EPD
—
—
15–30 A 15–30 A
LG
LJ
QO (B) EPE
—
—
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
Continued on next page
34
80043-712-06_A5Main_eng.fm Page 35 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
Max. System Voltage AC 1, 2
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
65,000
LL
1 Pole
2 Pole
3 Pole
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) GFI
—
15–30 A
—
DJ 400 A
QO (B) H
—
15–100 A
—
EJ, FJ
QO (B)
—
—
15–100 A
QO (B) VH
—
—
15–100 A
QO (B) H
—
15–100 A
—
QO (B)
—
—
15–100 A
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
35–150 A
FC_ or KC_34___
LJ
240 3P/3W or 240 1P/2W (two pole only) HJ, JJ
125,000
Type QO (B) EPD
FC_ or KC_24___
100,000
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6
HL, JL
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A 15–100 A
QO (B)
—
—
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
35–150 A
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
200,000
FI, KI, HR, JR
QO (B)
—
—
15–100 A
42,000
400 A Max. Class T3 Fuses
QO (B) VH
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–150 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B) VH
15–70 A
15–150 A
—
400 A Max. Class J Fuses
120/2407 1P/3W 65,000
400 A Max. Class T6 Fuses
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
Continued on next page
35
ENGLISH
Table 2:
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
80043-712-06_A5Main_eng.fm Page 36 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
Table 2: ENGLISH
Max. System Voltage AC 1, 2
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
100,000 120/2407 1P/3W
200,000
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
200 A Max. Class T3 Fuses
400 A Max. Class T3 Fuses 200 A Max. Class T6, J Fuses
208Y/120 3P/4W
80043-712-06 Rev. 02 11/2016
200,000 400 A Max. Class T3 Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6 Type
1 Pole
2 Pole
3 Pole
QO (B)
15–70 A
15–125 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B)
15–70 A
15–125 A
—
QO (B) GFI
—
—
15–50 A
QO (B) EPD
—
—
15–50 A
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
42,000
400 A Max. Class T3 Fuses
QO (B) VH
15–30 A
15–125 A
—
50,000
400 A Max. Class T3 Fuses
QO (B) VH
—
—
15–30 A
QO (B) VH
15–70 A
15–125 A
—
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
240/120 3P/4W 65,000
400 A Max. Class J Fuses
400 A Max. Class T6 Fuses
QO (B) DF
15–20 A
—
—
QO (B) VH
15–70 A
15–125 A
15–150 A
QO (B) AFI
15–20 A
—
—
Continued on next page
36
80043-712-06_A5Main_eng.fm Page 37 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
Max. System Voltage AC 1, 2
Series Connected Breaker Ratings (RMS Symmetrical) (continued) Max. Short Circuit Current Rating
100,000
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses
200 A Max. Class T3 Fuses
240/120 3P/4W 200 A Max. Class J or T6 Fuses 200,000
50,000
400 A Max. Class T3 Fuses
2 Pole
3 Pole
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) VH
—
—
15–30 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QOT
15–30 A
15–30 A
—
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
15–50 A
—
—
15–50 A
QO (B) VH
—
—
15–30 A
400 A Max. Class J Fuses
QO (B) VH
—
—
15–30 A
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) VH
—
—
15–150 A
QOB VH 1φ, 2W only
—
150 A
—
QO (B)
—
—
15–100 A
200 A Max. Class T3 Fuses 200 A Max. Class J or T6 Fuses
200,000
1 Pole
QO (B) EPE
400 A Max. Class T6 Fuses 100,000
Type
400 A Max. Class J or T6 Fuses
65,000 240 3P/3W or 240 1P/2W (two pole only)
Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges 3, 4, 5, 6
400 A Max. Class T3 Fuses
QO (B) VH
—
—
15–30 A
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B)
—
—
15–100 A
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
1
For shown circuit breakers rated less than this maximum voltage, the indicated short circuit current rating also applies, but at the voltage rating of the circuit breaker.
2
Short circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard.
37
ENGLISH
Table 2:
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
80043-712-06_A5Main_eng.fm Page 38 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
80043-712-06 Rev. 02 11/2016
ENGLISH
3
Suffixes HID, SWD, and SWN may also be applied to the applicable branch circuit breakers shown above. Suffix SWN may not be applied in combination with LC main breakers.
4
Where QO (B) circuit breakers are shown above, QO (B) H, QO (B) VH, and QH (B) circuit breakers may also be used.
5
Where QO (B) GFI circuit breakers are shown above, QO (B) EPD and/or QO (B) EPE circuit breakers may also be used. QO-EPE only comes in 3-pole construction.
6
Where QO (B) AFI circuit breakers are shown above, QO (B) CAFI circuit breakers may also be used.
7
Two-pole CAFI circuit breakers are only 120/240 Vac and may only be used on 120/240 VAC single phase 3 wire systems.
8
To achieve selective coordination, the rating of the DJ main circuit breaker must be at least two times greater than the ampere rating of any branch circuit breaker.
Table 3:
NQ Panel Mission Critical Breaker Selectivity
Maximum SCCR (RMS Symmetrical)
Integral or Remote Main Circuit Breakers
Branch Circuit Breakers Type1
J-W, 250 A
QO(B)-H
at 208Y/120 Vac or
L-W, 250 A
QO(B)-VH
at 240/120 Vac
at 208Y/120 Vac or
at 208Y/120 Vac or
3-pole
10–70
10–125
10–125
10–70
10–125
10–60
10–60
10–60
10–30
10–30
10–30
—
10–60
10–60
10–60
15–70
15–150
15–150
QH QO(B) J-W, 250 A
at 240/120 Vac Series Rated and Selective to 15 kA
2-pole
QO(B)
Fully Rated and Selective to 10 kA
Series Rated and Selective to 12 kA
1-pole
QO(B)-H QO(B)-VH QH QO(B)
J-W, 250 A
at 240/120 Vac
QO(B)-H QO(B)-VH QH QO(B)
J-W, 250 A Series Rated and Selective to 18 kA
QO(B)-H QO(B)-VH QH
at 208Y/120 Vac or
QO(B)
at 240/120 Vac L-W, 250 A
QO(B)-H QO(B)-VH QH QO(B)
Series Rated and Selective to 30 kA
L-W, 400 A
QO(B)-H
at 208Y/120 Vac or
L-W, 600 A
QO(B)-VH
at 240/120 Vac 1
Including AFI, CAFI, EPD and GFI Circuit Breakers
38
QH
80043-712-06_A5Main_eng.fm Page 39 Monday, January 23, 2017 1:44 PM
Table 4:
Maximum System Voltage AC
NQ/NQM Panelboards and QONQ Load Centers Appendix 1: Specifications
Short Circuit Current Rating1 for Main Lug Interiors with Sub-Feed or Feed-Through Lugs Maximum Current Rating
Branch Circuits2
Application
100
18, 30
SFL and FTL
—
SFL
6 inches (152.4 mm)
30, 42, 54, 72, 84, 96 225
42 30, 54, 72, 84, 96 30, 42, 54, 72, 84
240
96 400
— FTL
SFL
Maximum Short Circuit Current Rating4
10,000
6 inches (152.4 mm) —
25,000
—
10,000
30, 84
—
25,000
96
—
10,000
6 inches (152.4 mm)
25,000
12 inches (304.8 mm)
10,000
FTL
42, 54, 72 600
Adder3
30, 42, 54, 72, 84 96
FTL
1
This rating applies to main lug interiors, equipped with sub-feed or feed-through lugs, where the device feeding the interior is unknown or not a Square D brand device. Use of a Square D brand main circuit breaker ahead of these lugs will result in a rating equal to the rating of the breaker. Short circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard.
2
96 circuits with SPD has 84 usable branch circuits.
3
The adder is the additional length of the enclosure.
4
RMS symmetrical amperes, for three cycles.
CE Marking
•
Interiors with the "CE" mark meet the IEC 61439-1 and IEC 61439-2 standards.
•
Main lug interiors with the "CE" mark have been tested to withstand 10,000 RMS symmetrical amperes for 30 cycles.
•
Interiors with the "CE" mark are only approved for use with QOXD or QOBXD branch circuit breakers which carry the "CE" mark.
39
ENGLISH
80043-712-06 Rev. 02 11/2016
80043-712-06_A5Main_eng.fm Page 40 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 2: Accessory Kits
80043-712-06 Rev. 02 11/2016
Appendix 2: Accessory Kits ENGLISH
An assortment of field-installable accessory kits are available for NQ panelboards:
• • • •
Equipment Ground Bar Kits Oversized Lug Kits for 100–250 A Panelboards Sub-Feed Lug Kits for 100–400 A Panelboards Main Lug Kits — Mechanical Lug Kits—Aluminum — Mechanical Lug Kits—Copper — Versa-Crimp Compression Lug Kits—Aluminum — Versa-Crimp Compression Lug Kits—Copper
Equipment Ground Bar Kits Equipment ground bar kits, suitable for copper or aluminum wire, meet the grounding needs of NQ panelboards and QONQ load centers. Table 5:
Equipment Ground Bar Kits Specifications Panelboard
Branch Circuit 1–42 54–84
Mains Rating 600 A Maximum
Use Ground Bar Kit Catalog Number Aluminum1
Copper2
(1) PK27GTA
(1) PK27GTACU
(2) PK27GTA
(2) PK27GTACU
1
Aluminum bars suitable for 60° C or 75° C Copper or Aluminum conductors.
2
Copper bars suitable for 60° C or 75° C Copper conductors.
NOTE: Ground bar mounting locations are identified by the ground symbol into the back wall of the enclosure.
40
stamped
80043-712-06_A5Main_eng.fm Page 41 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
NQ/NQM Panelboards and QONQ Load Centers Appendix 2: Accessory Kits
ENGLISH
Oversized Lug Kits for 100–250 A Panelboards Oversized lug kits are available for applications where termination conductors of 3 AWG or larger are required for the neutral. Table 6:
Oversized Lug Kits for 100–250 A Panelboards Specifications
Circuit Breaker Rating
Kit Catalog Number
Wire Range
70 A
QO70AN
80–125 A
Q1100AN
(1) 4–1/0 Al/Cu ([1] 42.4–53.5 mm2)
125–150 A
Q1150AN
(1) 1–4/0 Al/Cu ([1] 42.4–107 mm2)
(1) 10–2 Al ([1] 5.76–33.6 mm2) (1)14–4 Cu ([1] 2.08–21.1 mm2)
Sub-Feed Lug Kits for 100–400 A Panelboards Sub-feed main lugs are available for 100, 225, or 400 A applications. Table 7:
1
Sub-Feed Lug Kits for 100–400 A Panelboards Specifications
Main Amps
Kit Catalog Number
100
NQSFL1
Maximum Circuits 18, 30
225
NQSFL2
301, 421, 541, 721, 841
400
NQSFL4
30, 42, 54, 72, 84
These panels require an additional 6 inches (152.4 mm) for the box and trim, for proper wire bending space.
41
80043-712-06_A5Main_eng.fm Page 42 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 2: Accessory Kits
80043-712-06 Rev. 02 11/2016
Main Lug Kits ENGLISH
Table 8:
Mechanical Lug Kits — Aluminum
Panelboard Amps
Kit Catalog Number
Wire Range
100
Standard
#6–2/0 AWG (13.3–67.43 mm2)
225
Standard
#6–350 kcmil (13.3–177.3 mm2)
400
(1) 1/0–750 kcmil (2) 1/0–350 kcmil
Standard
([1] 53.48–380 mm2) ([2] 53.48–177.3 mm2)
Standard
(2) 1/0–750 kcmil ([2] 53.48–380 mm2)
NQALM6A
(3) #6–250 kcmil ([3] 13.3–127 mm2)
600
Table 9:
Panelboard Amps
Kit Catalog Number
Wire Range
100
NQCUM1
#6–2/0 AWG (13.3–67.43 mm2)
225
NQCUM2
#6–250 kcmil (13.3–127 mm2)
400
NQCUM4
(1) 1/0–750 kcmil (2) 1/0–350 kcmil
600
NQCUM6
([1] 53.48–380 mm2) ([2] 53.48–177.3 mm2)
Table 10:
42
Mechanical Lug Kits — Copper
Versa-Crimp® Compression Lug Kits — Aluminum
Panelboard Amps
Kit Catalog Number
Wire Range
100
NQALV1
#8–1/0 AWG (8.36–53.48 mm2)
225
NQALV2
#4–300 kcmil (21.15–152 mm2)
400
NQALV4
600
NQALV6
(2) 2/0–500 kcmil ([2] 67.43–253.4 mm2)
Crimp Tool
VC6 (All)
VC6-3, VC6-FT
80043-712-06_A5Main_eng.fm Page 43 Monday, January 23, 2017 1:44 PM
80043-712-06 Rev. 02 11/2016
Versa-Crimp® Compression Lug Kits — Copper
Panelboard Amps
Kit Catalog Number
Wire Range
Crimp Tool
100
NQCUV1
#6–1/0 AWG (13.30–53.48 mm2)
VC6 (All), VC7 (All)
225
NQCUV2
2/0–300 kcmil (67.43–152 mm2)
VC6-3, VC7, VC6-FT, VC7-FT
400
NQCUV4
400–750 kcmil (202.7–380 mm2)
VC6-FT, VC7-FT, VC8
600
NQCUV6
(2) 250–500 kcmil ([2) 126.7–253.4 mm2)
VC6-3, VC7, VC6-FT, VC7-FT
ENGLISH
Table 11:
NQ/NQM Panelboards and QONQ Load Centers Appendix 2: Accessory Kits
43
80043-712-06_A5Main_eng.fm Page 44 Monday, January 23, 2017 1:44 PM
NQ/NQM Panelboards and QONQ Load Centers Appendix 2: Accessory Kits
ENGLISH 44
80043-712-06 Rev. 02 11/2016
ENGLISH
NQ/NQM Panelboards and QONQ Load Centers Instruction Bulletin
ENGLISH Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
Schneider Electric USA, Inc. 1415 S. Roselle Road Palatine, IL 60067 USA 1-888-SquareD (1-888-778-2733) www.us.SquareD.com
© 2007–2016 Schneider Electric All Rights Reserved Schneider Electric and Square D are trademarks owned by Schneider Electric Industries SAS or its affiliated companies. All other trademarks are the property of their respective owners. 80043-712-06 Rev. 02, 11/2016 Replaces 80043-712-06 Rev. 02, 06/2015
Para los tableros de alumbrado NQ/NQM y centros de carga QONQ
ESPAÑOL
Boletín de instrucciones Classe 1640
Boletín de instrucciones 80043-712-06 Rev. 02 11/2016 Conservar para uso futuro.
™
Categorías de riesgos y símbolos especiales
Asegúrese de leer detenidamente estas instrucciones y realice una inspección visual del equipo para familiarizarse con él antes de instalarlo, hacerlo funcionar o prestarle servicio de mantenimiento. Los siguientes mensajes especiales pueden aparecer en este boletín o en el equipo para advertirle sobre peligros potenciales o llamar su atención sobre cierta información que clarifica o simplifica un procedimiento. La adición de cualquiera de estos símbolos a una etiqueta de seguridad de “Peligro” o “Advertencia” indica la existencia de un peligro eléctrico que podrá causar lesiones personales si no se observan las instrucciones.
ESPAÑOL
Este es el símbolo de alerta de seguridad. Se usa para avisar sobre peligros potenciales de lesiones. Respete todos los mensajes de seguridad con este símbolo para evitar posibles lesiones o la muerte.
PELIGRO PELIGRO indica una situación de peligro inminente que, si no se evita, podrá causar la muerte o lesiones serias.
ADVERTENCIA ADVERTENCIA indica una situación potencialmente peligrosa que, si no se evita, puede causar la muerte o lesiones serias.
PRECAUCIÓN PRECAUCIÓN indica una situación potencialmente peligrosa que, si no se evita, puede causar lesiones menores o moderadas.
AVISO AVISO se usa para hacer notar prácticas no relacionadas con lesiones físicas. El símbolo de alerta de seguridad no se usa con esta palabra de indicación. NOTA: Proporciona información adicional para clarificar o simplificar un procedimiento.
Observe que
Solamente el personal especializado deberá instalar, hacer funcionar y prestar servicios de mantenimiento al equipo eléctrico. Schneider Electric no asume responsabilidad alguna por las consecuencias emergentes de la utilización de este material.
80043-712-06TOC_spa.fm Page 3 Monday, January 23, 2017 1:46 PM
80043-712-06 Rev. 02 11/2016
Para los tableros de alumbrado NQ/NQM y centros de carga QONQ Contenido
Introducción . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Precauciones de seguridad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Instalación . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Montaje de interiores en gabinetes marca Square D . . . . . . . . . . . . . . . . . . . . . . . 6 Montaje de sobreponer (gabinete montado en la pared) . . . . . . . . . . . . . . . . . 7 Montaje de empotrar (gabinete empotrado en la pared) . . . . . . . . . . . . . . . . . . 7 Instalación de la barra o cable de conexión del neutro . . . . . . . . . . . . . . . . . . . . . 9 Tableros de alumbrado NQ de 100 ó 250 A como máximo . . . . . . . . . . . . . . . 9 Centros de carga QONQ y tableros de alumbrado NQ de 400 ó 600 A como máximo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Instalación y desmontaje del interruptor automático QO y QOB . . . . . . . . . . . . . 13 Instalación de los interruptores automáticos QO y QOB . . . . . . . . . . . . . . . . 14 Desmontaje del interruptor automático QO y QOB . . . . . . . . . . . . . . . . . . . . . 14 Instrucciones para restablecer el interruptor automático . . . . . . . . . . . . . . . . . . . 16 Preparación del marco interior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Anexo 1: Especificaciones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Alambrado típico . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Interruptor automático principal o de subalimentación: DJ, FI, KI, H, J, LA, LC, LH, QB, QD, QG, QJ, QO(B)VH . . . . . . . . . . . . . . . . 19 Valores nominales del tablero . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Marcado CE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Anexo 2: Accesorios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Kits de barra de tierra del equipo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Kits de zapatas extra grande para los tableros de 100 a 250 A . . . . . . . . . . . . . . 42 Kits de zapatas de subalimentación para los tableros de 100 a 400 A . . . . . . . . 42 Kits de zapatas principales . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3
ESPAÑOL
Contenido
80043-712-06TOC_spa.fm Page 4 Monday, January 23, 2017 1:46 PM
Para los tableros de alumbrado NQ/NQM y centros de carga QONQ Contenido
80043-712-06 Rev. 02 11/2016
Lista de tablas Tabla 1: Tabla 2: Tabla 3: Tabla 4: ESPAÑOL
Tabla 5: Tabla 6: Tabla 7: Tabla 8: Tabla 9: Tabla 10: Tabla 11:
Alambrado típico del tablero de alumbrado . . . . . . . . . . . . . . . . . . . . . . 18 Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Selectividad de interruptores automáticos para aplicaciones críticas en tableros NQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Corriente nominal de cortocircuito para los interiores tipo zapatas principales equipados con zapatas de subalimentación o de paso . . . . 40 Especificaciones de los kits de barra de tierra del equipo . . . . . . . . . . . 41 Especificaciones de los kits de zapatas extra grande para los tableros de 100 a 250 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Especificaciones de los kits de zapatas de subalimentación para los tableros de 100 a 400 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Kits de zapatas mecánicas — Aluminio . . . . . . . . . . . . . . . . . . . . . . . . . 43 Kits de zapatas mecánicas — Cobre . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Kits de zapatas de compresión Versa-Crimp® — Aluminio . . . . . . . . . . 43 Kits de zapatas de compresión Versa-Crimp — Cobre . . . . . . . . . . . . . 44
Lista de figuras Figura 1: Figura 2: Figura 3: Figura 4: Figura 5: Figura 6: Figura 7: Figura 8:
Figura 9:
Figura 10:
4
Montaje del interior en gabinetes marca Square D . . . . . . . . . . . . . . . . . 8 Instalación de la barra de conexión del neutro—Tableros de alumbrado NQ de 100 ó 250 A como máximo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Instalación del cable de conexión del neutro— Centros de carga QONQ y tableros de alumbrado NQ de 400 ó 600 A como máximo . . . 12 Instalación y desmontaje de los interruptores automáticos QO y QOB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Posiciones de la palanca del interruptor automático . . . . . . . . . . . . . . . 16 Diagrama del marco interior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Diagrama del tablero con zapatas principales NQ/NQM de 100–225 A o interruptor automático principal de 100–250 A . . . . . . . . . 19 Diagrama del tablero NQ o centro de carga QONQ con zapatas principales de 400–600 A o interruptor automático principal con o sin zapatas de paso . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Diagrama del tablero NQ o centro de carga QONQ con interruptor automático principal de 400–600 A con zapatas de paso o interruptores automáticos de subalimentación . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Diagrama del tablero de alumbrado NQ típico con barras divididas . . . 22
80043-712-06 Rev. 02 11/2016
Tableros de alumbrado NQ/NQM y centros de carga QONQ Introducción
Introducción Este boletín contiene las instrucciones de instalación de los centros de carga QONQ y de los tableros de alumbrado NQ de interruptores automáticos marca Square D™. Estos centros de carga y tableros de alumbrado han sido registrados con Underwriters Laboratories (cULus) y aceptan interruptores automáticos derivados QO™ y QOB. ESPAÑOL
Para obtener asistencia técnica sobre la instalación de este tablero de alumbrado, póngase en contacto con el centro de información al cliente de Schneider Electric llamando al 1-888-778-2733 (en EUA). Consulte las etiquetas en el equipo para obtener información de seguridad y valores nominales. Con este documento se incluyen etiquetas adicionales del equipo.
Precauciones de seguridad
PELIGRO PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARQUEO • Utilice equipo de protección personal (EPP) apropiado y siga las prácticas de seguridad eléctrica establecidas por su Compañía, consulte la norma 70E de NFPA, Z462 de CSA y NOM-029-STPS. • Solamente el personal eléctrico calificado deberá instalar y prestar servicio de mantenimiento a este equipo. • Desenergice (O) el equipo antes de realizar cualquier trabajo dentro o fuera de él. • Siempre utilice un dispositivo detector de tensión adecuado para confirmar la desenergización del equipo. • Asegúrese de leer y entender todo el contenido de este boletín de instrucciones así como la publicación de normas NEMA PB 1.1 (incluida) antes de instalar, hacer funcionar o prestar servicio de mantenimiento a este equipo. • Las normas locales varían, se aceptan y hacen cumplir para fomentar la seguridad en instalaciones eléctricas. Es posible que necesite un permiso para realizar el trabajo eléctrico, y en algunos casos, algunos reglamentos pueden requerir una inspección del trabajo eléctrico efectuado. • Vuelva a colocar todos los dispositivos, las puertas y las cubiertas antes de volver a energizar el equipo. El incumplimiento de estas instrucciones podrá causar la muerte o lesiones serias.
5
Tableros de alumbrado NQ/NQM y centros de carga QONQ Instalación
80043-712-06 Rev. 02 11/2016
Instalación Esta sección proporciona instrucciones para los siguientes procedimientos de los tableros NQ y de los centros de carga QONQ:
ESPAÑOL
• •
Montaje de interiores en gabinetes marca Square D
•
“Instalación y desmontaje del interruptor automático QO y QOB” en la página 13
•
“Instrucciones para restablecer el interruptor automático” en la página 16
•
“Preparación del marco interior” en la página 17
“Instalación de la barra o cable de conexión del neutro” en la página 9
Montaje de interiores en gabinetes marca Square D Con este equipo, se ha incluido (por separado) la publicación de normas NEMA PB1.1 "Instrucciones generales apropiadas de instalación, funcionamiento y servicios de mantenimiento de tableros de alumbrado de 600 V o menos". Familiarícese con el contenido de este documento antes de continuar con los siguientes procedimientos. Si no recibió una copia de esta publicación, o si tiene alguna pregunta con respecto al equipo, póngase en contacto con su distribuidor o representante local de Schneider Electric.
AVISO PELIGRO DE DAÑO AL EQUIPO DEBIDO A CONEXIONES FLOJAS • Asegúrese de que todas las conexiones estén bien apretadas. • Consulte la etiqueta de información de par de apriete incluida con el tablero antes de apretar las conexiones. El incumplimiento de estas instrucciones puede causar daño al equipo. Para montar e instalar correctamente el interior de un tablero NQ o centro de carga QONQ, consulte la publicación de normas NEMA PB 1.1, y siga las instrucciones a continuación para “Montaje de sobreponer (gabinete montado en la pared)” en la página 7 o “Montaje de empotrar (gabinete empotrado en la pared)” en la página 7. 6
80043-712-06 Rev. 02 11/2016
Tableros de alumbrado NQ/NQM y centros de carga QONQ Instalación
Montaje de sobreponer (gabinete montado en la pared) 1. Monte el gabinete como se indica en la publicación de normas NEMA PB 1.1. 2. Retire el marco interior de sus soportes. 3. Instale el interior como se describe a continuación:
ESPAÑOL
a. Coloque el interior sobre los pernos del gabinete. No es necesario un tornillo elevador (vea la figura 1 en la página 8). b. Apriete las tuercas de seguridad en los rieles laterales del interior hasta que los rieles estén bien apoyados en la parte trasera del gabinete. c. Vuelva a montar el marco interior después de realizar el alambrado. 4. Si se utiliza como equipo de entrada de acometida, será necesaria una conexión del neutro. Consulte las instrucciones en “Instalación de la barra o cable de conexión del neutro” en la página 9. 5. Coloque las etiquetas del equipo (situadas en la bolsa de accesorios) siguiendo las instrucciones de la etiqueta colocada en la parte trasera del marco interior. Montaje de empotrar (gabinete empotrado en la pared) 1. Monte el gabinete como se indica en la publicación de normas NEMA PB 1.1. 2. Retire el marco interior de sus soportes. 3. Instale el interior como se describe a continuación: a. Rosque los (4) tornillos elevadores autorroscantes de 10-32 x 0,875 pulg. (incluidos con el marco para empotrar) en los rieles laterales. b. Coloque el interior sobre los pernos del gabinete (vea la figura 1 en la página 8). Coloque las tuercas de seguridad sobre los pernos del gabinete, sin apretarlas. c. Ajuste los tornillos de manera que el reborde del marco interior se encuentre 0,25 pulg (6,35 mm) de la pared. d. Apriete las tuercas de seguridad en los rieles laterales. e. Vuelva a montar el marco interior después de realizar el alambrado.
7
Tableros de alumbrado NQ/NQM y centros de carga QONQ Instalación
80043-712-06 Rev. 02 11/2016
4. Si se utiliza como equipo de entrada de acometida, será necesaria una conexión del neutro. Consulte las instrucciones en “Instalación de la barra o cable de conexión del neutro” en la página 9. 5. Coloque las etiquetas del equipo (situadas en la bolsa de accesorios) siguiendo las instrucciones de la etiqueta colocada en la parte trasera del marco interior. ESPAÑOL
Figura 1:
Montaje del interior en gabinetes marca Square D
Marco interior
0,25 pulg (6,35 mm)
Pared
Soporte del marco
Perno del gabinete
Tuerca de seguridad Gabinete
8
Tornillo elevador
Riel lateral
80043-712-06 Rev. 02 11/2016
Tableros de alumbrado NQ/NQM y centros de carga QONQ Instalación
Instalación de la barra o cable de conexión del neutro
Para conectar correctamente el neutro al tablero, siga las instrucciones para Tableros de alumbrado NQ de 100 ó 250 A como máximo o Centros de carga QONQ y tableros de alumbrado NQ de 400 ó 600 A como máximo en las páginas 9 y 11, respectivamente.
PELIGRO PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARQUEO • Utilice equipo de protección personal (EPP) apropiado y siga las prácticas de seguridad eléctrica establecidas por su Compañía, consulte la norma 70E de NFPA, Z462 de CSA y NOM-029-STPS. • Desenergice el equipo antes de realizar cualquier trabajo dentro o fuera de él. • La barra/cable de conexión del neutro deberá usarse sólo cuando el tablero de alumbrado ha sido instalado como equipo de acometida. • No mezcle los tornillos de montaje con los tornillos del marco interior. El incumplimiento de estas instrucciones podrá causar la muerte o lesiones serias. NOTA: Las piezas de la barra o cable de conexión del neutro se encuentran en la bolsa de accesorios incluida con el interior. Tableros de alumbrado NQ de 100 ó 250 A como máximo Para instalar la barra de conexión del neutro en un tablero NQ de 100 ó 250 A como máximo, consulte la figura 2 en la página 11 y siga las instrucciones a continuación. 1. Alinee la barra en el riel lateral, como se ilustra. NOTA: En algunas aplicaciones, tal vez sea necesario retirar la zapata (no ilustrada) antes de instalar la barra de conexión del neutro.
9
ESPAÑOL
La barra o el cable de conexión del neutro deberá usarse sólo cuando el tablero de alumbrado ha sido instalado como equipo de acometida.
Tableros de alumbrado NQ/NQM y centros de carga QONQ Instalación
80043-712-06 Rev. 02 11/2016
2. Inserte los dos tornillos de montaje, como se ilustra. Apriete el tornillo de 10-32 de 1,1–1,4 N•m (10–12 lbs-pulg) y el tornillo de 1/4-20 de 2,8–3,4 N•m (25–30 lbs-pulg).
ESPAÑOL
NOTA: Si la zapata fue retirada en el paso 1 arriba, vuélvala a instalar encima de la barra de conexión del neutro. Utilice el tornillo de montaje de zapatas de 1/4-20 x 11/16 pulg. en aplicaciones con zapata de paso, zapata de subalimentación, interruptor automático de subalimentación, o bien, con aplicaciones de neutro al 200%. Utilice el tornillo de montaje de zapatas de 1/4-20 x 7/8 pulg. en aplicaciones de 225 A con el neutro al 200% y con zapatas de paso, zapatas de subalimentación o interruptores automáticos de subalimentación. Los tornillos de montaje de la zapata vienen incluidos en la bolsa de accesorios de la barra.
10
80043-712-06 Rev. 02 11/2016
Figura 2:
Tableros de alumbrado NQ/NQM y centros de carga QONQ Instalación
Instalación de la barra de conexión del neutro— Tableros de alumbrado NQ de 100 ó 250 A como máximo Tornillos de montaje
1/4-20 x 9/16 in.
ESPAÑOL
Barra de conexión del neutro
10-32 x 5/16 in.
Barra de neutro Riel lateral
Centros de carga QONQ y tableros de alumbrado NQ de 400 ó 600 A como máximo Para instalar un cable de conexión del neutro en un centro de carga QONQ y tablero NQ de 400 ó 600 A como máximo, consulte la figura 3 y siga las instrucciones a continuación. 1. Alinee la zapata en el agujero de montaje del riel lateral, como se ilustra. 2. Apriete el tornillo de montaje de la zapata en el riel lateral de 1,1 a 1,4 N•m (10 a 12 lbs-pulg).
11
Tableros de alumbrado NQ/NQM y centros de carga QONQ Instalación
80043-712-06 Rev. 02 11/2016
3. Alinee el cable de conexión del neutro, como se ilustra, e insértelo en la zapata y agujeros de montaje del neutro. 4. Apriete ambos tornillos de sujeción del conductor del neutro y del conductor de la zapata de 5,1 a 5,6 N•m (45 a 50 lbs-pulg). Figura 3:
Instalación del cable de conexión del neutro— Centros de carga QONQ y tableros de alumbrado NQ de 400 ó 600 A como máximo
ESPAÑOL
Neutro Tornillo de sujeción del conductor del neutro Agujero de montaje del cable de conexión
Zapata Tornillo de montaje de la zapata Agujero de montaje del riel lateral Riel lateral
12
Tornillo de sujeción del conductor de la zapata
Cable de conexión del neutro
Agujero de montaje del cable de conexión
80043-712-06 Rev. 02 11/2016
Tableros de alumbrado NQ/NQM y centros de carga QONQ Instalación
Instalación y desmontaje del interruptor automático QO y QOB
PELIGRO • Utilice equipo de protección personal (EPP) apropiado y siga las prácticas de seguridad eléctrica establecidas por su Compañía, consulte la norma 70E de NFPA, Z462 de CSA y NOM-029-STPS. • Solamente el personal eléctrico calificado deberá instalar y prestar servicio de mantenimiento a este equipo. • Desenergice el equipo antes de realizar cualquier trabajo en él. • Siempre utilice un dispositivo detector de tensión adecuado para confirmar la desenergización del equipo. • Todos los espacios sin utilizar deben cubrirse con placas de relleno. • Vuelva a colocar todos los dispositivos, las puertas y las cubiertas antes de volver a energizar el equipo. El incumplimiento de estas instrucciones podrá causar la muerte o lesiones serias.
13
ESPAÑOL
PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARQUEO
Tableros de alumbrado NQ/NQM y centros de carga QONQ Instalación
80043-712-06 Rev. 02 11/2016
Instalación de los interruptores automáticos QO y QOB Consulte la figura 4 en la página 15 para completar las siguientes instrucciones. 1. Desenergice (Off/O) el tablero. 2. Mueva la palanca del interruptor automático QO(B) a la posición de abierto (Off/O). 3. Retire el marco interior. ESPAÑOL
4. Encaje en el riel de montaje el extremo del interruptor automático correspondiente a la terminal de alambrado del lado de carga. 5. Enganche el conector del lado de línea. Para los interruptores automáticos QO: a. Empuje hacia dentro hasta que las mordazas enchufables se enganchen completamente en el conector del lado de línea. Para los interruptores automáticos QOB: a. Empuje hacia adentro hasta que el conector del interruptor automático esté centrado con el agujero de montaje del conector. Enganche el tornillo en el agujero del conector y apriételo en los valores de par de apriete especificados en los diagramas de alambrado del interior. 6. Instale el conductor de carga. 7. Vuelva a instalar el marco interior. Desmontaje del interruptor automático QO y QOB Consulte la figura 4 en la página 15 para completar las siguientes instrucciones. 1. Desenergice (Off/O) el tablero. 2. Retire el marco interior. 3. Retire el conductor de carga. 4. Desenganche el conector derivado. Para los interruptores automáticos QO: a. Jale hacia fuera hasta que las mordazas enchufables se desenganchen completamente del conector del lado de línea. Para los interruptores automáticos QOB: a. Afloje el tornillo en el conector del interruptor automático y desengánchelo del conector del lado de línea. 14
80043-712-06 Rev. 02 11/2016
Tableros de alumbrado NQ/NQM y centros de carga QONQ Instalación
5. Desenganche el extremo del interruptor automático correspondiente a la terminal del riel de montaje . 6. Vuelva a instalar el marco interior. Instalación y desmontaje de los interruptores automáticos QO y QOB
Terminal
ESPAÑOL
Figura 4:
QO Mordaza enchufable
Riel Conector derivado
Terminal
QOB
CL Tornillo del conector atornillable
Riel Conector derivado
15
Tableros de alumbrado NQ/NQM y centros de carga QONQ Instalación
80043-712-06 Rev. 02 11/2016
Instrucciones para restablecer el interruptor automático Si se dispara el interruptor automático, la palanca se encontrará en la posición intermedia entre la posición de abierto (O/Off) y cerrado (I/On). Para restablecer el interruptor automático, mueva la palanca a la posición de abierto (O/Off) y luego a la posición de cerrado (I/On). Figura 5:
Posiciones de la palanca del interruptor automático
ESPAÑOL
Cerrado (I/On)
Abierto (O/Off)
Disparado
Palanca ON
OFF
16
ON
OFF
ON
OFF
80043-712-06 Rev. 02 11/2016
Tableros de alumbrado NQ/NQM y centros de carga QONQ Instalación
Preparación del marco interior
PELIGRO • Utilice equipo de protección personal (EPP) apropiado y siga las prácticas de seguridad eléctrica establecidas por su Compañía, consulte la norma 70E de NFPA, Z462 de CSA y NOM-029-STPS. • Antes de energizar el tablero de alumbrado, todos los espacios sin utilizar deben cubrirse con placas de relleno. • Vuelva a colocar todos los dispositivos, las puertas y las cubiertas antes de energizar este equipo. El incumplimiento de estas instrucciones podrá causar la muerte o lesiones serias. Figura 6:
Diagrama del marco interior Placas de relleno Marco interior
NOTA: La parte posterior del marco interior contiene una lista de números de catálogo para las placas de relleno compatibles correspondientes.
17
ESPAÑOL
PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARQUEO
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
80043-712-06 Rev. 02 11/2016
Anexo 1: Especificaciones Alambrado típico Tabla 1:
Alambrado típico del tablero de alumbrado1 Tableros de alumbrado de 1 fase
ESPAÑOL
Tensión de ~ (c.a.)
18
Tableros de alumbrado de 3 fases
Fase
Conductores
Fase
Conductores
208Y/120
—
—
3
4
120/240
1
3
—
—
2402
1
2
3
3
2403
1
3
—
—
240/1204
—
—
3
4, delta
1
El tablero de alumbrado incluye información adicional. Consulte el valor nominal del interruptor automático principal, si se usa.
2
Para este sistema no se utiliza el neutro y sólo se deben utilizar interruptores automáticos de 240 V~ (c.a.) como mínimo. No utilice interruptores automáticos de 120 ó 120/240 V~ (c.a.).
3
Para un sistema con fase "B" conectada a tierra, sólo se deben utilizar interruptores automáticos de 240 V~ (c.a.) como mínimo. No utilice interruptores automáticos de 120 ó 120/240 V~ (c.a.).
4
Cuando las conexiones son para un sistema delta, las fases "A" y "C" deben ser de 120 V a neutro, la fase "B" de 208 V a neutro. Conecte sólo interruptores automáticos de 240 V~ (c.a.) como mínimo. No utilice interruptores automáticos de 120 ó 120/240 V en la fase "B".
80043-712-06 Rev. 02 11/2016
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Interruptor automático principal o de subalimentación: DJ, FI, KI, H, J, LA, LC, LH, QB, QD, QG, QJ, QO(B)VH Figura 7:
Diagrama del tablero con zapatas principales NQ/NQM de 100–225 A o interruptor automático principal de 100–250 A
Tierra aislada
Interruptor automático principal de alimentación inversa
ESPAÑOL
(si está instalada)
(atornillable, si se usa)
Línea Tierra (si es necesaria)
Conexión al gabinete
Neutro
(si es necesaria)
Línea Interruptor automático principal (cuando está instalado)
Línea
19
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Figura 8:
80043-712-06 Rev. 02 11/2016
Diagrama del tablero NQ o centro de carga QONQ con zapatas principales de 400–600 A o interruptor automático principal con o sin zapatas de paso
Carga Zapatas de paso (si están instaladas)
ESPAÑOL
Tierra (si es necesaria)
Conexión al gabinete
Neutro
(si es necesaria)
Línea Interruptor automático principal (cuando está instalado)
Línea
20
80043-712-06 Rev. 02 11/2016
Diagrama del tablero NQ o centro de carga QONQ con interruptor automático principal de 400–600 A con zapatas de paso o interruptores automáticos de subalimentación
Carga
Carga
Interruptores automáticos de subalimentación)
ESPAÑOL
Figura 9:
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
(si están instalados)
Carga
Tierra (si es necesaria)
Conexión al gabinete
Neutro
(si es necesaria)
Línea Interruptor automático principal (cuando está instalado)
21
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Figura 10:
80043-712-06 Rev. 02 11/2016
Diagrama del tablero de alumbrado NQ típico con barras divididas
ESPAÑOL
Tierra (si es necesaria)
Conexión al gabinete
Neutro
(si es necesaria)
Línea Interruptor automático principal (cuando está instalado)
Línea
22
80043-712-06 Rev. 02 11/2016
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Valores nominales del tablero Consulte la sección 110-22 del NEC y de la NOM-001-SEDE y la norma 14-014 de CEC para obtener más información. La etiqueta del sistema en serie se encuentra en la bolsa de accesorios.
Tensión máxima del sistema de ~ 1, 2
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D 22 000
25 000
120/2407 1F/3H
MG
LD, HD, JD
HG, JG
65 000
LG
LJ
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos
QO (B)
15–30 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
—
QO (B) PL
15–30 A
15–60 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
—
QO (B) PL
15–30 A
15–60 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B) GFI
15–30 A
40–60 A
—
QO (B) EPD
15–30 A
40–60 A
—
Continúa en la siguiente página
23
ESPAÑOL
Tabla 2:
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tabla 2:
Tensión máxima del sistema de ~ 1, 2
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
ESPAÑOL
HJ, JJ
LJ
120/2407 1F/3H
80043-712-06 Rev. 02 11/2016
100 000
DJ 400 A
QJ
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos —
QO (B)
15–70 A
15–125 A
QO (B) VH
15–70 A
15–125 A
—
QO (B) PL
15–30 A
15–60 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
—
QO (B) H
—
15–100 A
— —
QO (B) GFI
—
15–30 A
QO (B) EPD
—
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
—
150 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) AS
15–30 A
15–30 A
—
QO (B) VH
—
150 A
— —
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
Continúa en la siguiente página
24
80043-712-06 Rev. 02 11/2016
Tensión máxima del sistema de ~ 1, 2
120/2407 1F/3H
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
125 000
HL, JL
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos —
QO (B)
15–70 A
15–125 A
QO (B) VH
15–70 A
15–125 A
—
QO (B) PL
15–30 A
15–60 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
ESPAÑOL
Tabla 2:
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–30 A
15–30 A
15–30 A
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–30 A
15–125 A
15–150 A
LA/LH (L), 34200MC 208Y/120 3F/4H
18 000
LA/LH (L), 34225MC LA/LH (L), 34250MC LA/LH (L), 34400MC
25 000
208Y/120 3F/4H
LD
DJ-W 150 A MC8
30 000
DJ-W 250 A MC8
DJ-W 600 A MC8
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–100 A
—
QO (B) VH
—
15–125 A
15–150 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B)
15–70 A
15–100 A
—
QO (B) VH
—
—
15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B)
15–70 A
15–100 A
—
QO (B) VH
—
—
15–150 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
Continúa en la siguiente página
25
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tabla 2:
Tensión máxima del sistema de ~ 1, 2
80043-712-06 Rev. 02 11/2016
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
ESPAÑOL LG
65 000
LJ
208Y/120 3F/4H
LL
100 000
DJ 400 A
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B) GFI
—
—
15–30 A
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B)
15–70 A
15–125 A
—
QO (B) VH
—
—
15–150 A —
QO (B) GFI
15–30 A
15–60 A
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Continúa en la siguiente página
26
80043-712-06 Rev. 02 11/2016
Tensión máxima del sistema de ~ 1, 2
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
QJ
208Y/120 3F/4H
100 000
LJ
240/120 3F/4H
22 000
QO (B) VH
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos
QO (B)
15–70 A
15–125 A
15–30 A
QO (B) VH
—
—
15–150 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
15–30 A
15–60 A
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
—
15–30 A
—
QO (B) EPD
—
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) PL
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Continúa en la siguiente página
27
ESPAÑOL
Tabla 2:
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tabla 2:
Tensión máxima del sistema de ~ 1, 2
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
ESPAÑOL QD
ED, FD 240/120 3F/4H
80043-712-06 Rev. 02 11/2016
25 000
KD
HD, JD
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos
QO (B)
15–70 A
15–125 A
15–30 A
QO (B) VH
—
—
35–150 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A 15–30 A
QO (B) AS
15–30 A
15–30 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Continúa en la siguiente página
28
80043-712-06 Rev. 02 11/2016
Tensión máxima del sistema de ~ 1, 2
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
25 000
LD
LA, MA
LC 400 A
240/120 3F/4H 42 000
LC 600 A
MG
65 000
LC 400 A
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–30 A
15–125 A
15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Q2L-H
—
100–225 A 100–225 A
QDL
—
70–225 A
QO (B)
15–70 A
15–70 A
70–225 A —
QO (B) VH
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B) VH
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B) VH
15–30 A
15–30 A
15–30 A
QO (B)
15–30 A
15–30 A
—
QO (B) VH
15–30 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Continúa en la siguiente página
29
ESPAÑOL
Tabla 2:
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tabla 2:
Tensión máxima del sistema de ~ 1, 2
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
ESPAÑOL
LC 600 A
DJ 400 A
240/120 3F/4H
80043-712-06 Rev. 02 11/2016
65 000
DJ_W
DJ, DG, DL 150–600 A
EG, FG, KG
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos
QO (B) VH
15–30 A
15–125 A
15–150 A
QO (B) GFI
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
—
—
15–150 A
QO (B) H
—
15–100 A
—
QO (B)
15–70 A
15–150 A
—
QO (B)-VH
—
QO (B) GFI
15–30 A
110–125 A 15–150 A 15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B) EPD
—
—
15–30 A
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Continúa en la siguiente página
30
80043-712-06 Rev. 02 11/2016
Tensión máxima del sistema de ~ 1, 2
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
QG
HG, JG
240/120 3F/4H
65 000
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos
QO (B)
15–70 A
15–125 A
15–30 A
QO (B) VH
—
—
35–150 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) PL
15–30 A
15–60 A
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
FC_ o KC_22___
QO (B)
15–70 A
15–100 A
15–100 A
FC_ o KC_34___
QO (B) AS
15–30 A
15–30 A
15–30 A
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
15–150 A
LG
LJ
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) GFI
15–30 A
40–60 A
—
QO (B) EPD
15–30 A
40–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
Continúa en la siguiente página
31
ESPAÑOL
Tabla 2:
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tabla 2:
Tensión máxima del sistema de ~ 1, 2
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
ESPAÑOL
65 000
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
FC_ o KC_22___
QO (B) GFI
15–30 A
15–30 A
—
FC_ o KC_34___
QO (B) AFI
15–20 A
—
— —
LL
DJ 400 A
EJ 240/120 3F/4H
80043-712-06 Rev. 02 11/2016
100 000 LJ
HJ, JJ
QO (B)
15–70 A
15–125 A
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
15–150 A —
QO (B) GFI
15–30 A
15–60 A
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
—
15–30 A
—
QO (B) EPD
—
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
— 15–100 A
QO (B)
15–70 A
15–125 A
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
35–150 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
Continúa en la siguiente página
32
80043-712-06 Rev. 02 11/2016
Tensión máxima del sistema de ~ 1, 2
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
125 000
HL, JL
240/120 3F/4H
200 000
22 000
FI, KI, HR, JR
QO (B) VH Q2-H
QD
240 3F/3H or 240 1F/2H (2 polos solamente) 25 000
ED, FD KD
HD, JD
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos 15–100 A
QO (B)
15–70 A
15–125 A
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
35–150 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
—
—
15–100 A 15–50 A
QO (B) GFI
—
—
QO (B) PL
—
15–30 A
—
QO (B)
—
—
15–30 A
QO (B)
—
—
15–30 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QO (B) PL
—
15–60 A
15–30 A
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) GFI
—
—
15–50 A
QO (B)
—
—
15–100 A
QO (B) GFI
—
—
15–50 A
QO (B)
—
—
15–100 A
QO (B)
—
—
15–100 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
—
—
15–50 A
Continúa en la siguiente página 33
ESPAÑOL
Tabla 2:
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tabla 2:
Tensión máxima del sistema de ~ 1, 2
80043-712-06 Rev. 02 11/2016
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
ESPAÑOL
25 000
42 000
LD
1 polo
2 polos
3 polos 15–150 A
QO (B) VH
—
—
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
LA, MA
QDL
—
70–225 A
70–225 A
QO (B) VH
—
—
15–100 A
LC 600 A
QO (B) VH
—
—
15–100 A
MG
QO (B) VH
—
—
150 A
LC 400 A
QO (B) VH
—
—
15–100 A
LC 600 A
QO (B) VH
—
—
15–30 A
QO (B) VH
—
—
15–150 A
DJ, DG, DL 150–600 A EG, FG, KG
QO (B) H
—
15–100 A
—
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B)
—
—
15–100 A
QO (B) GFI
—
—
15–50 A
QO (B)
—
—
15–30 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QG, HG, JG
QO (B) PL
—
—
15–30 A
QO (B)
—
—
15–100 A
HG, JG
QO (B) VH
—
—
35–150 A
QG
65 000
Tipo
LC 400 A
DJ 400 A
240 3F/3H o 240 1F/2H (2 polos solamente)
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6
QO (B) H
—
15–100 A
—
FC_ o KC_22___
QO (B)
—
—
15–100 A
FC_ o KC_34___
QO (B) AS
—
15–30 A
15–30 A
QO (B) VH
—
—
15–150 A
QO (B) H
—
15–100 A
—
QO (B) EPD
—
—
15–30 A 15–30 A
LG
LJ LL
QO (B) EPE
—
—
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
Continúa en la siguiente página 34
80043-712-06 Rev. 02 11/2016
Tensión máxima del sistema de ~ 1, 2
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
Tipo
1 polo
2 polos
3 polos
QO (B) GFI
—
15–30 A
—
DJ 400 A
QO (B) H
—
15–100 A
—
EJ, FJ
QO (B)
—
—
15–100 A
QO (B) VH
—
—
15–100 A
QO (B) H
—
15–100 A
—
QO (B)
—
—
15–100 A
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
35–150 A
FC_ o KC_24___ FC_ o KC_34___
100 000 240 3F/3H o 240 1F/2H (2 polos solamente)
120/2407 1F/3H
LJ
HJ, JJ
125 000
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6
HL, JL
ESPAÑOL
Tabla 2:
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A 15–100 A
QO (B)
—
—
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
35–150 A
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
200 000
FI, KI, HR, JR
QO (B)
—
—
15–100 A
42 000
Fusibles clase T3 de 400 A como máx.
QO (B) VH
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–150 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B) VH
15–70 A
15–150 A
—
Fusibles clase J de 400 A como máx. 65 000 Fusibles clase T6 de 400 A como máx.
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
Continúa en la siguiente página
35
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tabla 2:
Tensión máxima del sistema de ~ 1, 2
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
ESPAÑOL
100 000
Fusibles clase T3 de 200 A como máx.
120/2407 1F/3H
200 000
Fusibles clase T3 de 400 A como máx.
Fusibles clase T6 o J de 200 A como máx. 208Y/120 3F/4H
80043-712-06 Rev. 02 11/2016
200 000 Fusibles clase T3 de 400 A como máx.
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos
QO (B)
15–70 A
15–125 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B)
15–70 A
15–125 A
—
QO (B) GFI
—
—
15–50 A
QO (B) EPD
—
—
15–50 A
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
42 000
Fusibles clase T3 de 400 A como máx.
QO (B) VH
15–30 A
15–125 A
—
50 000
Fusibles clase T3 de 400 A como máx.
QO (B) VH
—
—
15–30 A
QO (B) VH
15–70 A
15–125 A
—
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
240/120 3F/4H 65 000
Fusibles clase J de 400 A como máx.
Fusibles clase T6 de 400 A como máx.
QO (B) DF
15–20 A
—
—
QO (B) VH
15–70 A
15–125 A
15–150 A
QO (B) AFI
15–20 A
—
—
Continúa en la siguiente página
36
80043-712-06 Rev. 02 11/2016
Tensión máxima del sistema de ~ 1, 2
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D
100 000
Fusibles clase T3 de 200 A como máx.
240/120 3F/4H
200 000
50 000
240 3F/3H o 240 1F/2H (2 polos solamente)
Tipo
1 polo
2 polos
3 polos
QO (B)
15–70 A
15–125 A
15–100 A
QO (B) VH
—
—
15–30 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QOT
15–30 A
15–30 A
—
Fusibles clase J o T6 de 200 A como máx.
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B)
15–70 A
15–125 A
15–100 A
Fusibles clase T3 de 400 A como máx.
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
Fusibles clase J o T6 de 400 A como máx.
QO (B) VH
—
—
15–30 A
Fusibles clase J de 400 A como máx.
QO (B) VH
—
—
15–30 A
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) VH
—
—
15–150 A
QOB VH 1φ, 2H solamente
—
150 A
—
QO (B)
—
—
15–100 A
QO (B) VH
—
—
15–30 A
65 000 Fusibles clase T6 de 400 A como máx.
100 000
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6
Fusibles clase T3 de 200 A como máx.
Continúa en la siguiente página
37
ESPAÑOL
Tabla 2:
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tabla 2:
Tensión máxima del sistema de ~ 1, 2
ESPAÑOL
240 3F/3H o 240 1F/2H (2 polos solamente)
80043-712-06 Rev. 02 11/2016
Valores nominales de los interruptores automáticos conectados en serie (simétrico rcm) (continuación) Interruptores Corriente automáticos nominal principales integrales máx. de o remotos y fusibles cortoprincipales remotos circuito marca Square D Fusibles clase J o T6 de 200 A como máx. 200 000
Fusibles clase T3 de 400 A como máx.
Designación de número de catálogo de los interruptores automáticos derivados marca Square D y gamas de corriente permitidas3, 4, 5, 6 Tipo
1 polo
2 polos
3 polos
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A 15–100 A
QO (B)
—
—
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
1
Para los interruptores automáticos que figuran en esta tabla con una tensión máxima inferior a ésta, la corriente nominal de cortocircuito indicada también es aplicable pero en la tensión nominal del interruptor automático.
2
Las pruebas de cortocircuito son conducidas entre el 100 y 105% de la tensión nominal máxima del tablero combinado I-Line.
3
Los sufijos HID, SWD y SWN también pueden ser aplicables para los interruptores automáticos derivados que se muestran arriba. Es posible que el sufijo SWN no sea aplicable en combinación con los interruptores automáticos principales LC.
4
Es posible utilizar los interruptores automáticos QO (B) H, QO (B) VH y QH (B) donde se muestran los interruptores QO (B).
5
Es posible utilizar los interruptores automáticos QO (B) EPD y/o QO (B) EPE donde se muestran los interruptores QO (B) GFI.
6
Es posible utilizar los interruptores automáticos QO (B) CAFI donde se muestran los interruptores QO (B) AFI.
7
Los interruptores automáticos CAFI de dos polos son únicamente de 120/240 V~ y pueden ser utilizados en sistemas de una fase y 3 hilos de 120/240 V~ solamente.
8
Para lograr una coordinación selectiva, el valor nominal del interruptor automático principal DJ debe ser, por lo menos, dos veces mayor que el valor nominal en amperes de cualquier interruptor automático derivado.
38
80043-712-06 Rev. 02 11/2016
Selectividad de interruptores automáticos para aplicaciones críticas en tableros NQ
SCCR máxima (simétricos rcm)
Valor nominal total y selectivo hasta 10 kA en 208 Y/120 V~ o en 240/120 V~ Valor nominal en serie y selectivo hasta 12 kA en 208Y/120 V~ o en 240/120 V~ Valor nominal en serie y selectivo hasta 15 kA en 208Y/120 V~ o en 240/120 V~
Interruptores automáticos principales integral o remoto
Interruptores automáticos derivados Tipo1
1-polo
2-polos
3-polos
10–70
10–125
10–125
10–70
10–125
10–60
10–60
10–60
10–30
10–30
10–30
—
10–60
10–60
10–60
15–70
15–150
15–150
QO(B) J-W, 250 A
QO(B)-H
L-W, 250 A
QO(B)-VH
ESPAÑOL
Tabla 3:
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
QH QO(B) J-W, 250 A
QO(B)-H QO(B)-VH QH QO(B)
J-W, 250 A
QO(B)-H QO(B)-VH QH QO(B)
J-W, 250 A Valor nominal en serie y selectivo hasta 18 kA en 208Y/120 V~ o en 240/120 V~
QO(B)-H QO(B)-VH QH QO(B)
L-W, 250 A
QO(B)-H QO(B)-VH QH
Valor nominal en serie y selectivo hasta 30 kA en 208Y/120 V~ o en 240/120 V~ 1
QO(B) L-W, 400 A
QO(B)-H
L-W, 600 A
QO(B)-VH QH
Incluyendo los interruptores automáticos AFI, CAFI, EPD y GFI.
39
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 1: Especificaciones
Tabla 4:
Tensión máxima del sistema, ~ (c.a.)
80043-712-06 Rev. 02 11/2016
Corriente nominal de cortocircuito para los interiores tipo zapatas principales equipados con zapatas de subalimentación o de paso1 Corriente nominal máxima
Circuitos derivados
Aplicación
Adicionador2
Corriente nominal máxima de cortocircuito 3
100
18, 30
ESPAÑOL
30, 42, 54, 72, 84, 96 225
30, 42, 54, 72, 84 96 400
—
SFL
6 pulgadas (152.4 mm)
42 30, 54, 72, 84, 96
240
SFL and FTL
— FTL
SFL
30, 84 96
FTL
42, 54, 72 600
30, 42, 54, 72, 84 96
FTL
10,000
6 pulgadas (152.4 mm) —
25,000
—
10,000
—
25,000
—
10,000
6 pulgadas (152.4 mm)
25,000
12 pulgadas (304.8 mm)
10,000
1
Estos valores nominales son aplicables para los interiores con zapatas principales, equipados con zapatas de subalimentación o de paso, donde el dispositivo que alimenta al interior es desconocido o no es de marca Square D. El uso de un interruptor automático principal marca Square D frente a estas zapatas producirá un valor nominal igual al del interruptor. Las pruebas de cortocircuito son conducidas entre el 100 y 105% de la tensión nominal máxima del tablero de alumbrado.
2
El adicionador es la longitud adicional del gabinete.
3
Amperes simétricos de rcm para tres ciclos.
Marcado CE
40
•
Interiores con el marcado "CE" cumplen con las normas IEC 61439-1 e IEC 61439-2.
•
Los interiores con zapatas principales y marcado "CE" han sido probados para soportar 10 000 amperes simétricos rcm durante 30 ciclos.
•
Los interiores con el marcado "CE" sólo están aprobados para su uso con interruptores automáticos derivados QOXD o QOBXD que llevan el marcado "CE".
80043-712-06 Rev. 02 11/2016
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 2: Accesorios
Anexo 2: Accesorios Se encuentran disponibles una variedad de accesorios de instalación en campo para los tableros de alumbrado NQ:
• • •
Kits de barra de tierra del equipo
•
Kits de zapatas principales
Kits de zapatas extra grande para los tableros de 100 a 250 A
ESPAÑOL
Kits de zapatas de subalimentación para los tableros de 100 a 400 A — Kits de zapatas mecánicas — Aluminio — Kits de zapatas mecánicas — Cobre — Kits de zapatas de compresión Versa-Crimp®— Aluminio — Kits de zapatas de compresión Versa-Crimp — Cobre
Kits de barra de tierra del equipo Los kits de barra de tierra del equipo son adecuados para conductores de cobre o aluminio y cumplen con los requisitos de conexión a tierra de los tableros NQ y centros de carga QONQ. Tabla 5:
Especificaciones de los kits de barra de tierra del equipo
Tablero de alumbrado Número de circuitos 1–42 54–84
Capacidad nominal 600 A máx.
Utilice el kit de barra de puesta a tierra con número de catálogo Aluminio1
Cobre2
(1) PK27GTA
(1) PK27GTACU
(2) PK27GTA
(2) PK27GTACU
1
Barras de aluminio adecuadas para conductores de Cu o Al para 60° C o 75° C
2
Barras de cobre adecuadas para conductores de Cu para 60° C o 75° C
NOTA: Las ubicaciones de montaje de la barra de puesta a tierra han sido identificadas por el símbolo de tierra estampado en la pared trasera del gabinete.
41
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 2: Accesorios
80043-712-06 Rev. 02 11/2016
Kits de zapatas extra grande para los tableros de 100 a 250 A Se encuentran disponibles kits de zapatas extra grande para aplicaciones donde el neutro requiere conductores de terminación de 3 AWG o de tamaño mayor. Tabla 6:
Especificaciones de los kits de zapatas extra grande para los tableros de 100 a 250 A
ESPAÑOL
Valor nominal del interruptor No. de catálogo del kit automático
Tamaño del conductor (1) 10–2 Al (1) 5,76–33,6 mm2
70 A
QO70AN
80–125 A
Q1100AN
(1) 4–1/0 Al/Cu (1) 42,4–53,5 mm2
125–150 A
Q1150AN
(1) 1–4/0 Al/Cu (1) 42,4–107 mm2
(1)14–4 Cu (1) 2,08–21,1 mm2
Kits de zapatas de subalimentación para los tableros de 100 a 400 A Se encuentran disponibles kits de zapatas principales de subalimentación para las aplicaciones de 100, 225 ó 400 A. Tabla 7:
Especificaciones de los kits de zapatas de subalimentación para los tableros de 100 a 400 A
Capacidad nominal de las barras (A)
No. de catálogo del kit
Cantidad máxima de circuitos
100
NQSFL1
18, 30
225
NQSFL2
301, 421, 541, 721, 841
400
NQSFL4
30, 42, 54, 72, 84
1
42
Estos tableros requieren una longitud adicional de 152,4 mm (6 pulgadas) para el gabinete y marco para tener el espacio necesario para el doblez de los conductores.
80043-712-06 Rev. 02 11/2016
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 2: Accesorios
Kits de zapatas principales Kits de zapatas mecánicas — Aluminio
Capacidad nominal del tablero (A)
No. de catálogo del kit
Tamaño del conductor
100
Estándar
#6–2/0 AWG 13,3–67,43 mm2
225
Estándar
#6–350 kcmil 13,3–177,3 mm2
400
Estándar
(1) 1/0–750 kcmil (2) 1/0–350 kcmil (1) 53,48–380 mm2 (2) 53,48–177,3 mm2
Estándar
(2) 1/0–750 kcmil (2) 53,48–380 mm2
NQALM6A
(3) #6–250 kcmil (3) 13,3–127 mm2
600
Tabla 9:
Kits de zapatas mecánicas — Cobre
Capacidad nominal del tablero (A)
No. de catálogo del kit
Tamaño del conductor
100
NQCUM1
#6–2/0 AWG 13,3–67,43 mm2
225
NQCUM2
#6–250 kcmil 13,3–127 mm2
400
NQCUM4
(1) 1/0–750 kcmil (2) 1/0–350 kcmil
600
NQCUM6
(1) 53,48–380 mm2 (2) 53,48–177,3 mm2
Tabla 10:
ESPAÑOL
Tabla 8:
Kits de zapatas de compresión Versa-Crimp® — Aluminio
Capacidad nominal del tablero (A)
No. de catálogo del kit
Tamaño del conductor
100
NQALV1
#8–1/0 AWG 8,36–53,48 mm2
225
NQALV2
#4–300 kcmil 21,15–152 mm2
400
NQALV4
600
NQALV6
(2) 2/0–500 kcmil (2) 67,43–253,4 mm2
Herramienta de compresión
VC6 (todos)
VC6-3, VC6-FT
43
Tableros de alumbrado NQ/NQM y centros de carga QONQ Anexo 2: Accesorios
Tabla 11:
80043-712-06 Rev. 02 11/2016
Kits de zapatas de compresión Versa-Crimp — Cobre
ESPAÑOL
Capacidad nominal del tablero (A)
No. de catálogo del kit
Tamaño del conductor
Herramienta de compresión
100
NQCUV1
#6–1/0 AWG 13,30–53,48 mm2
VC6 (todos), VC7 (todos)
225
NQCUV2
2/0–300 kcmil 67,43–152 mm2
VC6-3, VC7, VC6-FT, VC7-FT
400
NQCUV4
400–750 kcmil 202,7–380 mm2
VC6-FT, VC7-FT, VC8
600
NQCUV6
(2) 250–500 kcmil (2) 126,7–253,4 mm2
VC6-3, VC7, VC6-FT, VC7-FT
44
ESPAÑOL
Tableros de alumbrado NQ/NQM y centros de carga QONQ Boletín de instrucciones
ESPAÑOL Solamente el personal especializado deberá instalar, hacer funcionar y prestar servicios de mantenimiento al equipo eléctrico. Schneider Electric no asume responsabilidad alguna por las consecuencias emergentes de la utilización de este material. Importado en México por:
Schneider Electric México, S.A. de C.V. Calz. J. Rojo Gómez 1121-A Col. Gpe. del Moral 09300 México, D.F. Tel. 55-5804-5000 www.schneider-electric.com.mx
© 2007–2016 Schneider Electric Reservados todos los derechos Schneider Electric y Square D son marcas comerciales de Schneider Electric Industries SAS o sus compañías afiliadas. Todas las otras marcas comerciales son propiedad de sus respectivos propietarios. 80043-712-06 Rev. 02, 11/2016 Reemplaza 80043-712-06 Rev. 02, 06/2015
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Directives d’utilisation Classe 1640
Directives d’utilisation 80043-712-06 Rev. 02 11/2016
FRANÇAIS
À conserver pour usage ultérieur.
™
Catégories de dangers et symboles spéciaux
Lisez soigneusement ces directives et examinez l’appareillage afin de vous familiariser avec lui avant son installation, son fonctionnement ou son entretien. Les messages spéciaux qui suivent peuvent apparaître dans ce document ou sur l’appareillage. Ils vous avertissent de dangers potentiels ou attirent votre attention sur des renseignements pouvant éclaircir ou simplifier une procédure. L’ajout de l’un ou l’autre des symboles à une étiquette de sécurité « Danger » ou « Avertissement » vous indique qu’un danger électrique existe et qu’il pourra y avoir des blessures corporelles si les directives ne sont pas suivies. Ceci est le symbole d’une alerte de sécurité. Il sert à vous avertir d’un danger potentiel de blessures corporelles. Respectez toutes les consignes de sécurité accompagnant ce symbole pour éviter toute situation potentielle de blessure ou de mort.
DANGER FRANÇAIS
DANGER indique une situation de danger imminent qui, si elle n’est pas évitée, entraînera la mort ou des blessures graves.
AVERTISSEMENT AVERTISSEMENT indique une situation de danger potentiel qui, si elle n’est pas évitée, peut entraîner la mort ou des blessures graves.
ATTENTION ATTENTION indique une situation de danger potentiel qui, si elle n’est pas évitée, peut entraîner des blessures mineures ou modérées.
AVIS AVIS est utilisé pour commenter des pratiques sans rapport avec les blessures physiques. Le symbole d'alerte de sécurité n'est pas employé avec ce mot de signalement. REMARQUE : Fournit des renseignements complémentaires pour clarifier ou simplifier une procédure.
Veuillez noter
Seul un personnel qualifié doit effectuer l’installation, l’utilisation, l’entretien et la maintenance du matériel électrique. Schneider Electric n’assume aucune responsabilité des conséquences éventuelles découlant de l’utilisation de cette documentation.
80043-712-06 Rev. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Table des matières
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Mesures de sécurité . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Montage de l’intérieur pour coffrets de la marque Square D . . . . . . . . . . . . . . . . . 6 Montage en surface (coffret monté sur un mur) . . . . . . . . . . . . . . . . . . . . . . . . 7 Montage encastré (coffret encastré dans le mur) . . . . . . . . . . . . . . . . . . . . . . . 7 Installation du câble/tresse de mise à la masse du neutre . . . . . . . . . . . . . . . . . . . 9 Panneaux de distribution NQ de 100 ou 250 A au maximum . . . . . . . . . . . . . . 9 Centres de distribution QONQ et panneaux de distribution NQ de 400 ou 600 A au max. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Installation et démontage des disjoncteurs QO et QOB . . . . . . . . . . . . . . . . . . . . 13 Installation des disjoncteurs QO et QOB . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Démontage des disjoncteurs QO et QOB . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Directives de réarmement du disjoncteur . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Préparation de la garniture intérieure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Annexe 1 : Spécifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Câblage typique . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Disjoncteur principal intégré ou de sous-alimentation : DJ, FI, KI, H, J, LA, LC, LH, QB, QD, QG, QJ, QO(B)VH . . . . . . . . . . . . . . . . 19 Valeurs nominales du panneau de distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Marquage CE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Annexe 2 : Accessoires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Kits de barre de m.à.l.t. de l’appareil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Kits de cosses surdimensionnées pour les panneaux de distribution de 100 à 250 A 42 Kits de cosses de sous-alimentation pour les panneaux de distribution de 100 à 400 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Kit de cosse principale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3
FRANÇAIS
Table des matières
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Table des matières
80043-712-06 Rev. 02 11/2016
Liste des tableaux Tableau 1 : Tableau 2 : Tableau 3 : Tableau 4 : Tableau 5 : Tableau 6 : Tableau 7 :
FRANÇAIS
Tableau 8 : Tableau 9 : Tableau 10 : Tableau 11 :
Câblage typique du panneau de distribution . . . . . . . . . . . . . . . . . . . . . 18 Val. nom. de disjoncteurs raccordés en série (RMS sym.). . . . . . . . . . . 23 Sélectivité de disjoncteur critique pour panneau NQ . . . . . . . . . . . . . . . 39 Courant nominal de court-circuit pour intérieurs à cosses principales avec cosses de traversée ou de sous-alimentation . . . . . . . . . . . . . . . . 40 Spécifications des kits de barre de m.à.l.t. de l’appareil . . . . . . . . . . . . 41 Spécifications du kit de cosses surdimensionnées pour les panneaux de distribution de 100 à 250 A. . . . . . . . . . . . . . . . . . . . . . . . 42 Spécifications du kit de cosses de sous-alimentation pour les panneaux de distribution de 100 à 400 A. . . . . . . . . . . . . . . . . . . . . . . . 42 Kits de cosses mécaniques — Aluminum . . . . . . . . . . . . . . . . . . . . . . . 43 Kits de cosses mécaniques — Cuivre . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Kits de cosses à compression Versa-Crimp® — Aluminum . . . . . . . . . 43 Kits de cosses à compression Versa-Crimp — Cuivre. . . . . . . . . . . . . . 43
Liste des figures Figure 1 : Figure 2 : Figure 3 :
Figure 4 : Figure 5 : Figure 6 : Figure 7 : Figure 8 :
Figure 9 :
Figure 10 :
4
Montage de l’intérieur des coffrets de la marque Square D . . . . . . . . . . . 8 Installation de la tresse de mise à la masse — Panneaux de distribution NQ de 100 ou 250 A au maximum . . . . . . . . 11 Installation du câble de mise à la masse — Centres de distribution QONQ et panneaux de distribution NQ de 400 ou 600 A au maximum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Installation et démontage des disjoncteurs QO et QOB. . . . . . . . . . . . . 15 Positions de la manette du disjoncteur. . . . . . . . . . . . . . . . . . . . . . . . . . 16 Schéma de la garniture intérieure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Schéma de cosses principales NQ/NQM de 100 à 225 A ou disjoncteur principal de 100 à 250 A . . . . . . . . . . . . . . . . . . . . . . . . . 19 Schéma de panneau NQ ou centre de distribution QONQ à cosses principales ou disjoncteur principal de 400 à 600 A avec ou sans cosses de traversée . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Schéma de panneau NQ ou centre de distribution QONQ à disjoncteur principal de 400 à 600 A avec cosses de traversée ou de disjoncteurs de sous-alimentation . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Schéma de panneau de distribution NQ typique avec barre-bus fendue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Introduction
Introduction Ce bulletin contient les directives pour l'installation des centres de distribution QONQ et des panneaux de distribution NQ à disjoncteurs de la marque Square DMC. Ces centres et panneaux de distribution sont inscrits UL (cULus) et acceptent les disjoncteurs de dérivation QOMC et QOB.
Consulter les étiquettes sur l’appareil pour les renseignements de capacité et de sécurité. Des étiquettes supplémentaires pour l’appareil sont fournies avec ce document.
Mesures de sécurité
DANGER RISQUE D'ÉLECTROCUTION, D'EXPLOSION OU ÉCLAIR D'ARC ÉLECTRIQUE • Portez un équipement de protection personnelle (ÉPP) approprié et observez les méthodes de travail électrique sécuritaire. Voir NFPA 70E, CSA Z462 ou NOM-029STPS. • Seul un personnel qualifié doit effectuer l'installation et l'entretien de cet appareil. • Coupez l'alimentation de l'appareil avant d'y travailler. • Utilisez toujours un dispositif de détection de tension ayant une valeur nominale appropriée pour s'assurer que l'alimentation est coupée. • Lisez et comprenez entièrement ces directives d’utilisation et la publication des normes NEMA PB 1.1 incluse avant d’installer, d’utiliser ou d’assurer l’entretien de cet appareil. • Les codes locaux varient mais sont adoptés et appliqués pour assurer des installations électriques sécuritaires. C’est peut-être nécessaire d’avoir un permis pour exécuter des travaux sur des circuits électriques et certains codes peuvent exiger que le travail électrique accompli soit inspecté. • Replacez tous les dispositifs, les portes et les couvercles avant de mettre l'appareil sous tension. Si ces directives ne sont pas respectées, cela entraînera la mort ou des blessures graves.
5
FRANÇAIS
Pour obtenir une assistance technique sur l’installation de ce panneau de distribution, contacter le centre d’informations à la clientèle Schneider Electric au 1-888-778-2733 (É.-U.).
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Installation
80043-712-06 Rév. 02 11/2016
Installation Cette section fournit les directives pour les procédures suivantes concernant les panneaux de distribution NQ et les centres de distribution QONQ :
• •
« Montage de l’intérieur pour coffrets de la marque Square D » ci-après.
•
« Installation et démontage des disjoncteurs QO et QOB » à la page 13
• •
« Directives de réarmement du disjoncteur » à la page 16
« Installation du câble/tresse de mise à la masse du neutre » à la page 9
« Préparation de la garniture intérieure » à la page 17
Montage de l’intérieur pour coffrets de la marque Square D FRANÇAIS
Une publication séparée, intitulée « Directives générales pour l’installation, le fonctionnement et l’entretien des panneaux de distribution d’une valeur nominale de 600 V ou moins » (NEMA PB1.1) a été fournie avec cet appareil. Se familiariser avec le contenu de ce document avant d’entreprendre l’une quelconque des procédures ci-après. Si un exemplaire de cette publication n’était pas joint, ou si des questions se posent concernant cet appareil, contacter le distributeur local ou un représentant de Schneider Electric.
AVIS RISQUE DE DOMMAGES MATÉRIELS DUS À UN RACCORDEMENT DÉFAIT OU LÂCHE • Assurez-vous que tous les raccordements sont correctement serrés. • Reportez-vous à l’étiquette de renseignements sur les couples de serrage, placée sur le panneau de distribution, avant de serrer les raccordements. Si ces directives ne sont pas respectées, cela peut entraîner des dommages matériels. Pour monter et installer correctement l’intérieur du panneau de distribution NQ ou du centre de distribution QONQ, consulter la publication sur les normes NEMA PB 1.1 et observer les directives ciaprès concernant « Montage en surface (coffret monté sur un mur) » ou « Montage encastré (coffret encastré dans le mur) ». 6
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Installation
Montage en surface (coffret monté sur un mur) 1. Monter le coffret en suivant les directives de la publication des normes NEMA PB 1.1. 2. Enlever la garniture intérieure des supports de garniture. 3. Installer l’intérieur comme décrit ci-après : a. Placer l’intérieur sur les goujons du coffret. Une vis d’élévation n’est pas nécessaire (voir la figure 1 à la 8). b. Serrer les écrous Keps sur les rails latéraux de l’intérieur jusqu’à ce que les rails se trouvent contre l’arrière du coffret. 4. Si l’appareil est utilisé comme appareil d’entrée de service, une fixation (mise à la masse) du neutre est nécessaire. Voir les directives dans la section « Installation du câble/tresse de mise à la masse du neutre » à la page 9. 5. Poser les étiquettes de l’appareil (fournies dans le sac de l’assortiment) comme indiqué aux directives, au dos de la feuille d’étiquettes de l’appareil. Montage encastré (coffret encastré dans le mur) 1. Monter le coffret comme indiqué dans la publication des normes NEMA PB 1.1. 2. Enlever la garniture intérieure des supports de garniture. 3. Installer l’intérieur comme décrit ci-après : a. Visser les (4) vis d'élévation auto-taraudeuses de 10-32 x 0,875 po fournies avec la garniture encastrée dans les rails latéraux. b. Placer l’intérieur sur les goujons du coffret (voir la figure 1 à la 8). Placer les écrous Keps sur les goujons du coffret, mais ne pas les serrer. c. Ajuster les vis de façon à ce que le rebord de la garniture intérieure soit à environ 0,25 po (6,35 mm) du mur. d. Serrer les écrous Keps sur les rails latéraux. e. Remonter la garniture intérieure une fois le câblage effectué. 4. Si l’appareil est utilisé comme appareil d’entrée de service, une fixation (mise à la masse) du neutre est nécessaire. Voir les directives dans la section « Installation du câble/tresse de mise à
7
FRANÇAIS
c. Remonter la garniture intérieure une fois le câblage effectué.
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Installation
80043-712-06 Rév. 02 11/2016
la masse du neutre » à la page 9. 5. Poser les étiquettes de l’appareil (fournies dans le sac de l’assortiment) comme indiqué aux directives, au dos de la feuille d’étiquettes de l’appareil. Figure 1 :
Montage de l’intérieur des coffrets de la marque Square D
Garniture intérieure
0,25 po (6,35 mm)
Mur
FRANÇAIS
Support de la garniture
Goujon du coffret
Écrou Keps Coffret
8
Vis d'élévation
Rail latéral
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Installation
Installation du câble/tresse de mise à la masse du neutre Le câble ou la tresse de mise à la masse du neutre ne doit être utilisé que lorsque le panneau de distribution est installé comme appareil de service. Pour fixer correctement le neutre au panneau de distribution, suivre les directives pour « Panneaux de distribution NQ de 100 ou 250 A au maximum » ou pour « Centres de distribution QONQ et panneaux de distribution NQ de 400 ou 600 A au max. » aux pages 9 et 11, respectivement.
DANGER RISQUE D'ÉLECTROCUTION, D'EXPLOSION OU ÉCLAIR D'ARC ÉLECTRIQUE FRANÇAIS
• Portez un équipement de protection personnelle (ÉPP) approprié et observez les méthodes de travail électrique sécuritaire. Voir NFPA 70E, CSA Z462 ou NOM-029-STPS. • Coupez l'alimentation de l'appareil avant d'y travailler. • La tresse ou le câble de mise à la masse principal ne doit être utilisé que lorsque le panneau de distribution est installé comme appareil de service. • Ne mélangez pas les vis de montage avec les vis de la garniture intérieure. Si ces directives ne sont pas respectées, cela entraînera la mort ou des blessures graves. REMARQUE : Les pièces de la tresse ou du câble de mise à la masse se trouvent dans le sac de l’assortiment fourni avec l’intérieur. Panneaux de distribution NQ de 100 ou 250 A au maximum Pour installer une tresse de mise à la masse du neutre sur un panneau de distribution NQ de 100 ou 250 A au maximum, se reporter à la figure 2, 11, et suivre les directives ci-dessous. 1. Aligner la tresse de mise à la masse sur le rail latéral, comme illustré. REMARQUE : Pour certaines applications, il peut être nécessaire de retirer la cosse (non représentée) avant d’installer la tresse.
9
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Installation
80043-712-06 Rév. 02 11/2016
2. Insérer les deux vis de montage, comme illustré. Serrer la vis de 10-32 au couple de 1,1 à 1,4 N•m (10 à 12 lb-po) et la vis de 1/4-20 au couple de 2,86 à 3,4 N•m (25 à 30 lb-po). REMARQUE : Si la cosse a été retirée au point 1 ci-dessus, la réinstaller sur le dessus de la tresse de mise à la masse. Utiliser la vis de montage de 1/4-20 x 11/16 po avec les applications à cosse de traversée, cosse de sous-alimentation, disjoncteur de sous-alimentation ou neutre de 200 %. Utiliser la vis de montage de cosse de 1/4-20 x 7/8 po sur des applications de 225 A avec un neutre de 200 % et avec cosses de traversée, cosses de sousalimentation ou disjoncteurs de sous-alimentation. Les vis de montage de cosses sont fournies dans le sac de l’assortiment de la tresse de mise à la masse.
FRANÇAIS 10
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Installation
Figure 2 :
Installation de la tresse de mise à la masse — Panneaux de distribution NQ de 100 ou 250 A au maximum 1/4-20 x 9/16 in.
Vis de montage
Tresse de mise à la masse
FRANÇAIS
10-32 x 5/16 in.
Barre-bus de neutre Rail latéral
Centres de distribution QONQ et panneaux de distribution NQ de 400 ou 600 A au max. Pour installer un câble de mise à la masse du neutre sur un panneau de distribution NQ de 400 ou 600 A maximum et un centre de distribution QONQ, se reporter à la figure 3 et suivre les directives cidessous. 1. Aligner la cosse sur le trou de montage du rail latéral, comme illustré. 2. Serrer la vis de montage de la cosse sur le rail latéral au couple de 1,1 à 1,4 N•m (10 à 12 lb-po). 11
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Installation
80043-712-06 Rév. 02 11/2016
3. Aligner le câble de mise à la masse, comme illustré, et l’insérer dans la cosse et les trous de montage du neutre. 4. Serrer la vis de fixation des fils de la cosse et la vis de fixation des fils du neutre au couple de 5,1 à 5,6 N•m (45 à 50 lb-po). Figure 3 :
Installation du câble de mise à la masse — Centres de distribution QONQ et panneaux de distribution NQ de 400 ou 600 A au maximum
Neutre
FRANÇAIS
Vis de fixation des fils du neutre Trou de montage du câble de mise à la masse
Cosse Vis de montage de la cosse
Trou de montage du rail latéral Rail latéral
12
Vis de fixation des fils de la cosse Câble de mise à la masse
Trou de montage du câble de mise à la masse
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Installation
Installation et démontage des disjoncteurs QO et QOB
DANGER RISQUE D'ÉLECTROCUTION, D'EXPLOSION OU ÉCLAIR D'ARC ÉLECTRIQUE • Portez un équipement de protection personnelle (ÉPP) approprié et observez les méthodes de travail électrique sécuritaire. Voir NFPA 70E, CSA Z462 ou NOM-029-STPS. • Seul un personnel qualifié doit effectuer l'installation et l'entretien de cet appareil. • Utilisez toujours un dispositif de détection de tension ayant une valeur nominale appropriée pour s'assurer que l'alimentation est coupée. • Tous les espaces inutilisés doivent être remplis avec des plaques de remplissage. • Replacez tous les dispositifs, les portes et les couvercles avant de mettre l'appareil sous tension. Si ces directives ne sont pas respectées, cela entraînera la mort ou des blessures graves.
13
FRANÇAIS
• Coupez l'alimentation de l'appareil avant d'y travailler.
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Installation
80043-712-06 Rév. 02 11/2016
Installation des disjoncteurs QO et QOB Pour les directives suivantes, consulter la figure 4 à la 15. 1. Couper (O) toutes les alimentations du panneau de distribution. 2. Mettre le disjoncteur hors tension (O). 3. Enlever la garniture intérieure. 4. Emboîter l'extrémité de la borne de raccordement du disjoncteur sur le rail de montage. 5. Engager le connecteur de dérivation. Pour les disjoncteurs QO : a. pousser vers l'intérieur jusqu'à ce que les mâchoires enfichables s'engagent totalement dans le connecteur de dérivation. FRANÇAIS
Pour les disjoncteurs QOB : a. pousser vers l'intérieur jusqu'à ce que le connecteur du disjoncteur soit centré sur le trou de montage du connecteur de dérivation. Engager la vis dans le trou du connecteur de dérivation et serrer aux valeurs de couple indiquées sur le schéma de câblage et de couple de l’intérieur. 6. Installer le fil de charge. 7. Réinstaller la garniture intérieure. Démontage des disjoncteurs QO et QOB Pour les directives suivantes, consulter la figure 4 à la 15. 1. Couper (O) toutes les alimentations du panneau de distribution. 2. Enlever la garniture intérieure. 3. Retirer le fil de charge. 4. Dégager le connecteur de dérivation. Pour les disjoncteurs QO : a. Tirer vers l'extérieur jusqu'à ce que les mâchoires enfichables se dégagent totalement du connecteur de dérivation. Pour les disjoncteurs QOB : a. Desserrer la vis du connecteur du disjoncteur et séparer le disjoncteur du connecteur de dérivation.
14
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Installation
5. Déboîter du rail de montage l’extrémité de la borne de raccordement du disjoncteur. 6. Réinstaller la garniture intérieure. Figure 4 :
Installation et démontage des disjoncteurs QO et QOB
Borne de raccordement
QO Mâchoire enfichable
FRANÇAIS
Rail Connecteur de dérivation
Borne de raccordement
QOB
CL Vis de connecteur boulonnée
Rail Connecteur de dérivation
15
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Installation
80043-712-06 Rév. 02 11/2016
Directives de réarmement du disjoncteur Si le disjoncteur est déclenché, la manette se trouvera en position moyenne entre marche (I/ON) et arrêt (O/OFF). Pour réarmer le disjoncteur, mettre la manette à la position d’arrêt, puis à la position de marche. Figure 5 : Manette
Positions de la manette du disjoncteur Marche (I/ON) ON
OFF
FRANÇAIS 16
Arrêt (O/OFF) ON
OFF
Déclenché ON
OFF
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Installation
Préparation de la garniture intérieure
DANGER RISQUE D'ÉLECTROCUTION, D'EXPLOSION OU ÉCLAIR D'ARC ÉLECTRIQUE • Portez un équipement de protection personnelle (ÉPP) approprié et observez les méthodes de travail électrique sécuritaire. Voir NFPA 70E, CSA Z462 ou NOM-029-STPS. • Avant de mettre le panneau de distribution sous tension, tous les espaces inutilisés doivent être remplis avec des plaques de remplissage. • Replacez tous les dispositifs, les portes et les couvercles avant de mettre l'appareil sous tension.
Figure 6 :
FRANÇAIS
Si ces directives ne sont pas respectées, cela entraînera la mort ou des blessures graves. Schéma de la garniture intérieure Plaques de remplissage Garniture intérieure
REMARQUE : L’arrière de la garniture intérieure donne la liste des numéros de catalogue des plaques de remplissage compatibles correspondants.
17
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
80043-712-06 Rév. 02 11/2016
Annexe 1 : Spécifications Câblage typique Tableau 1 : Câblage typique du panneau de distribution1 Panneaux de distribution Panneaux de distribution monophasés triphasés Tension ca
FRANÇAIS 18
Phase
Fils
Phase
Fils
208Y/120
—
—
3
4
120/240
1
3
—
—
2402
1
2
3
3
2403
1
3
—
—
240/1204
—
—
3
4, en triangle
1
Des informations supplémentaires sont fournies sur le panneau de distribution. Voir la valeur nominale du disjoncteur principal, si utilisé.
2
Pour ce système, le neutre n’est pas utilisé et seuls les disjoncteurs à tension nominale minimale de 240 Vca doivent être utilisés. Ne pas utiliser des disjoncteurs d’une tension nominale de 120 V ou de 120/240 Vca.
3
Pour un système de phase « B » mis à la terre, seuls des disjoncteurs d'une tension nominale minimale de 240 Vca doivent être utilisés. Ne pas utiliser des disjoncteurs d’une tension nominale de 120 V ou de 120/240 Vca.
4
Lorsqu’elles sont câblées pour un système en triangle, les phases « A » et « C » doivent être de 120 V au neutre, la phase « B » doit être de 208 V au neutre. Raccorder seulement des disjoncteurs d’une tension nominale minimale de 240 Vca. Ne pas utiliser des disjoncteurs d’une tension nominale de 120 V ou 120/240 V pour la phase « B ».
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
Disjoncteur principal intégré ou de sous-alimentation : DJ, FI, KI, H, J, LA, LC, LH, QB, QD, QG, QJ, QO(B)VH Figure 7 :
Schéma de cosses principales NQ/NQM de 100 à 225 A ou disjoncteur principal de 100 à 250 A
M.à.l.t. isolée
Disjoncteur principal rétro-alimenté
(lorsqu'elle est installée)
(doit être boulonné, si utilisé)
FRANÇAIS
Ligne
Terre (lorsque nécessaire)
Fixation (mise à la masse) du coffret
Neutre
(lorsque nécessaire)
Ligne
Disjoncteur principal intégré (lorsqu'il est installé)
Ligne
19
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
Figure 8 :
80043-712-06 Rév. 02 11/2016
Schéma de panneau NQ ou centre de distribution QONQ à cosses principales ou disjoncteur principal de 400 à 600 A avec ou sans cosses de traversée
Charge Cosses de traversée (lorsqu'elles sont installées)
FRANÇAIS
Terre (lorsque nécessaire)
Fixation (mise à la masse) du coffret
Neutre
(lorsque nécessaire)
Ligne
Disjoncteur principal intégré (lorsqu'il est installé)
Ligne
20
80043-712-06 Rév. 02 11/2016
Schéma de panneau NQ ou centre de distribution QONQ à disjoncteur principal de 400 à 600 A avec cosses de traversée ou de disjoncteurs de sous-alimentation
Charge
Charge
Disjoncteur(s) de sous-alimentation (lorsqu'il est installé)
Charge FRANÇAIS
Figure 9 :
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
Terre (lorsque nécessaire)
Fixation (mise à la masse) du coffret
Neutre
(lorsque nécessaire)
Ligne Disjoncteur principal intégré (lorsqu'il est installé)
21
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
80043-712-06 Rév. 02 11/2016
Figure 10 : Schéma de panneau de distribution NQ typique avec barre-bus fendue
FRANÇAIS
Terre (lorsque nécessaire)
Fixation (mise à la masse) du coffret
Neutre
(lorsque nécessaire)
Ligne Disjoncteur principal intégré (lorsqu'il est installé)
22
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
Valeurs nominales du panneau de distribution Se reporter au NEC (É.-U.) section 110-22, et au CCE règle 14-014 pour des informations supplémentaires. L’étiquette pour un système qualifié pour utilisation en série se trouve dans le sac de l'assortiment. Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
25 000
120/2407
MG
LD, HD, JD
HG, JG
1P/3F
65 000
LG
LJ
QO (B)
15–30 A
—
QO (B)
15–70 A
15–125 A
— —
QO (B) VH
15–70 A
15–125 A
— —
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
— —
QO (B) DF
15–20 A
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
— —
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
— —
QO (B) DF
15–20 A
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
— —
QO (B) DF
15–20 A
—
QO (B) GFI
15–30 A
40–60 A
—
QO (B) EPD
15–30 A
40–60 A
—
FRANÇAIS
22 000
Page suivante
23
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
80043-712-06 Rév. 02 11/2016
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
HJ, JJ
FRANÇAIS
LJ
120/2407 1P/3F
100 000
DJ 400 A
QJ
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
— —
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
— —
QO (B) AFI
15–20 A
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
— —
QO (B) H
—
15–100 A
QO (B) GFI
—
15–30 A
—
QO (B) EPD
—
15–60 A
— —
QO (B) AFI
15–20 A
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
—
150 A
—
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
— —
QO (B) AFI
15–20 A
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
— —
QO (B)
15–70 A
15–125 A
QO (B) AS
15–30 A
15–30 A
—
QO (B) VH
—
150 A
—
QO (B) PL
15–30 A
15–60 A
—
QO (B) GFI
15–30 A
15–60 A
— —
QO (B) AFI
15–20 A
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
— Page suivante
24
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite)
120/2407 1P/3F
125 000
HL, JL
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A
— —
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B)
15–30 A
15–30 A
15–30 A
—
LA/LH (L), 34200MC 208Y/120 3P/4F
18 000
LA/LH (L), 34225MC LA/LH (L), 34250MC LA/LH (L), 34400MC
25 000
LD
DJ-W 150 A MC8
208Y/120 3P/4F
30 000
DJ-W 250 A MC8
DJ-W 600 A MC8
QO (B)
15–70 A
15–125 A
QO (B) VH
15–30 A
15–125 A 15–150 A
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–100 A
—
QO (B) VH
—
15–125 A 15–150 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B)
15–70 A
15–100 A
—
QO (B) VH
—
—
15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B)
15–70 A
15–100 A
—
QO (B) VH
—
—
15–150 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
— Page suivante
25
FRANÇAIS
Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
80043-712-06 Rév. 02 11/2016
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
LG
FRANÇAIS
208Y/120 3P/4F
65 000
LJ
LL
QO (B)
15–70 A
15–125 A
QO (B) VH
15–70 A
15–125 A 15–150 A
—
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A 15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B) GFI
—
—
15–30 A
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A Page suivante
26
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite)
DJ 400 A
208Y/120 3P/4F
100 000
QJ
LJ
QO (B)
15–70 A
15–125 A
—
QO (B) VH
—
—
15–150 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–30 A
QO (B) VH
—
—
15–150 A
QO (B) PL
15–30 A
15–60 A
15–30 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
15–30 A
15–60 A
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–70 A
15–125 A 15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
—
15–30 A
—
QO (B) EPD
—
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
27
FRANÇAIS
Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
80043-712-06 Rév. 02 11/2016
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
22 000
QO (B) VH
FRANÇAIS
240/120 3P/4F QD
25 000
ED, FD
QO (B)
15–70 A
QO (B) GFI
15–30 A
15–125 A 15–100 A 15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A 15–50 A
QO (B) EPE
—
—
QO (B) PL
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
15–30 A
QO (B) VH
—
—
35–150 A
QO (B) PL
15–30 A
15–60 A
15–30 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A 15–50 A
QO (B) EPE
—
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
—
—
QO (B) DF
15–20 A
QO (B)
15–70 A
15–125 A 15–100 A
QO (B) GFI
15–30 A
15–60 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
15–50 A
— Page suivante
28
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
HD, JD
25 000
240/120 3P/4F LD
LA, MA
42 000 LC 400 A
15–70 A
15–125 A 15–100 A
15–30 A
15–30 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
15–30 A
QO (B)
15–70 A
QO (B) VH
—
15–125 A 15–100 A —
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
35–150 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
15–30 A
15–125 A 15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
—
100–225 A
100–225 A
70–225 A 70–225 A
Q2L-H QDL
—
QO (B)
15–70 A
15–70 A
QO (B) VH
15–70 A
15–125 A 15–100 A
QO (B) GFI
15–30 A
15–60 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
— 15–30 A
— Page suivante
29
FRANÇAIS
KD
QO (B) QO (B) AS
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
80043-712-06 Rév. 02 11/2016
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
42 000
LC 600 A
MG
FRANÇAIS
LC 400 A
LC 600 A 240/120 3P/4F DJ 400 A 65 000
DJ_W
DJ, DG, DL 150–600 A
EG, FG, KG
QO (B) VH
15–70 A
15–125 A 15–100 A
QO (B) GFI
15–30 A
15–60 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
15–30 A
QO (B) DF
15–20 A
—
—
QO (B) VH
15–30 A
15–30 A
15–30 A —
QO (B)
15–30 A
15–30 A
QO (B) VH
15–30 A
15–125 A 15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B) VH
15–30 A
15–125 A 15–150 A
QO (B) GFI
—
—
QO (B) AFI
15–20 A
—
15–30 A —
QO (B) CAFI
15–20 A
—
— —
QO (B) DF
15–20 A
—
QO (B)
15–70 A
15–125 A
—
QO (B) VH
—
—
15–150 A
QO (B) H
—
15–100 A
—
QO (B)
15–70 A
15–150 A
—
QO (B)-VH
—
110–125 A
15–150 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B) EPD
—
—
15–30 A
QO (B)
15–70 A
15–125 A 15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
— Page suivante
30
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
HG, JG
240/120 3P/4F
65 000
15–70 A
15–125 A
15–30 A
—
—
35–150 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) PL
15–30 A
15–60 A
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
—
—
QO (B) DF
15–20 A
QO (B)
15–70 A
15–125 A 15–100 A
QO (B) VH
—
—
QO (B) H
—
15–100 A
35–150 A —
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
—
—
QO (B) DF
15–20 A
FC_ o KC_22___
QO (B)
15–70 A
15–100 A 15–100 A
FC_ o KC_34___
QO (B) AS
15–30 A
15–30 A
15–30 A —
LG
LJ
QO (B)
15–70 A
15–125 A
QO (B) VH
15–70 A
15–125 A 15–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
15–30 A
15–60 A
15–30 A
QO (B) EPD
15–30 A
15–60 A
15–30 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
— —
QO (B) DF
15–20 A
—
QO (B)
15–70 A
15–125 A
—
QO (B) GFI
15–30 A
40–60 A
—
QO (B) EPD
15–30 A
40–60 A
15–30 A
QO (B) EPE
—
—
15–30 A Page suivante
31
FRANÇAIS
QG
QO (B) QO (B) VH
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
80043-712-06 Rév. 02 11/2016
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles 65 000
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
FC_ ou KC_22___
QO (B) GFI
15–30 A
15–30 A
—
FC_ ou KC_34___
QO (B) AFI
15–20 A
—
— —
LL
FRANÇAIS
DJ 400 A
EJ 240/120 3P/4F 100 000 LJ
HJ, JJ
QO (B)
15–70 A
15–125 A
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
15–150 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
—
—
QO (B) DF
15–20 A
QO (B)
15–70 A
15–125 A 15–100 A
QO (B)
15–70 A
15–125 A
QO (B) VH
15–70 A
15–125 A 15–150 A
—
QO (B) H
—
15–100 A
QO (B) GFI
—
15–30 A
— —
QO (B) EPD
—
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
—
—
QO (B) DF
15–20 A
QO (B)
15–70 A
15–125 A 15–100 A
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
35–150 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
— Page suivante
32
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
HL, JL
240/120 3P/4F
200 000
22 000
FI, KI, HR, JR
QO (B) VH Q2-H
QD
240 3P/3F ou 240 1P/2F (2 pôles uniquement) 25 000
ED, FD KD
HD, JD
15–70 A —
15–100 A
15–125 A 15–100 A —
QO (B) VH
—
—
35–150 A 15–30 A
QO (B) PL
15–30 A
15–60 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
—
—
QO (B) DF
15–20 A
QO (B)
15–70 A
15–125 A 15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
QO (B) DF
15–20 A
—
—
QO (B)
—
—
15–100 A 15–50 A
QO (B) GFI
—
—
QO (B) PL
—
15–30 A
—
QO (B)
—
—
15–30 A
QO (B)
—
—
15–30 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QO (B) PL
—
15–60 A
15–30 A
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) GFI
—
—
15–50 A
QO (B)
—
—
15–100 A
QO (B) GFI
—
—
15–50 A
QO (B)
—
—
15–100 A
QO (B)
—
—
15–100 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QO (B) GFI
—
—
15–50 A Page suivante 33
FRANÇAIS
125 000
QO (B) QO (B) H
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
80043-712-06 Rév. 02 11/2016
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles 25 000
42 000
QO (B) VH
—
—
15–150 A
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
LA, MA
QDL
—
LC 400 A
QO (B) VH
—
—
15–100 A
LC 600 A
QO (B) VH
—
—
15–100 A
MG
QO (B) VH
—
—
150 A
LC 400 A
QO (B) VH
—
—
15–100 A
LD
FRANÇAIS
LC 600 A DJ 400 A DJ, DG, DL 150–600 A EG, FG, KG 240 3P/3F ou 240 1P/2F (2 pôles uniquement)
QO (B) VH
—
—
15–30 A
QO (B) VH
—
—
15–150 A
QO (B) H
—
15–100 A
—
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B)
—
—
15–100 A
QO (B) GFI
—
—
15–50 A
QO (B)
—
—
15–30 A
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
QG, HG, JG
QO (B) PL
—
—
15–30 A
QO (B)
—
—
15–100 A
HG, JG
QO (B) VH
—
—
35–150 A
QO (B) H
—
15–100 A
—
FC_ ou KC_22___
QO (B)
—
—
15–100 A
FC_ ou KC_34___
QO (B) AS
—
15–30 A
15–30 A
QO (B) VH
—
—
15–150 A
QO (B) H
—
15–100 A
—
QO (B) EPD
—
—
15–30 A
QG
65 000
70–225 A 70–225 A
LG
LJ LL
QO (B) EPE
—
—
15–30 A
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A Page suivante
34
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
QO (B) GFI
—
15–30 A
DJ 400 A
QO (B) H
—
15–100 A
—
EJ, FJ
QO (B)
—
—
15–100 A 15–100 A
FC_ ou KC_34___
100 000 240 3P/3F ou 240 1P/2F (2 pôles uniquement)
LJ
HJ, JJ
125 000
HL, JL
—
QO (B) VH
—
—
QO (B) H
—
15–100 A
—
QO (B)
—
—
15–100 A
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
35–150 A
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A 15–100 A
QO (B)
—
—
QO (B) H
—
15–100 A
—
QO (B) VH
—
—
35–150 A
QO (B) EPD
—
—
15–30 A
QO (B) EPE
—
—
15–30 A
200 000
FI, KI, HR, JR
QO (B)
—
—
15–100 A
42 000
400 A max. Fusibles classe T3
QO (B) VH
15–70 A
15–125 A
—
400 A max. Fusibles classe J
120/2407 1P/3F 65 000
400 A max. Fusibles classe T6
QO (B) VH
15–70 A
15–150 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
—
QO (B) VH
15–70 A
15–150 A
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
— Page suivante
35
FRANÇAIS
FC_ ou KC_24___
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
80043-712-06 Rév. 02 11/2016
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
100 000 120/2407 1P/3F
200 000
200 A max. Fusibles classe T3
FRANÇAIS
400 A max. Fusibles classe T3 200 A max. Fusibles classe T6 ou J
208Y/120 3P/4F
200 000 400 A max. Fusibles classe T3
QO (B)
15–70 A
15–125 A
QO (B) GFI
15–30 A
15–60 A
— —
QO (B) EPD
15–30 A
15–60 A
— —
QO (B) AFI
15–20 A
—
QO (B) CAFI
15–20 A
15–20 A
—
QO (B) DF
15–20 A
—
— —
QO (B)
15–70 A
15–125 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
—
QO (B)
15–70 A
15–125 A
—
QO (B) GFI
—
—
15–50 A
—
15–50 A
QO (B) EPD
—
QO (B)
15–70 A
15–125 A 15–100 A
QO (B) GFI
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) EPD
15–30 A
15–60 A
15–50 A
42 000
400 A max. Fusibles classe T3
QO (B) VH
15–30 A
15–125 A
—
50 000
400 A max. Fusibles classe T3
QO (B) VH
—
—
15–30 A
QO (B) VH
15–70 A
15–125 A
—
QO (B) EPD
—
—
15–50 A 15–50 A
240/120 3P/4F 65 000
400 A max. Fusibles classe J
400 A max. Fusibles classe T6
QO (B) EPE
—
—
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
—
—
QO (B) DF
15–20 A
QO (B) VH
15–70 A
QO (B) AFI
15–20 A
15–125 A 15–150 A —
— Page suivante
36
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
200 A max. Fusibles classe T3
240/120 3P/4F 200 A max. Fusibles classe J ou T6 200 000
50 000
240 3P/3F ou 240 1P/2F (2 pôles uniquement)
400 A max. Fusibles classe T3
—
15–125 A 15–100 A —
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) AFI
15–20 A
—
—
QO (B) CAFI
15–20 A
—
—
15–30 A
QO (B) DF
15–20 A
—
—
QOT
15–30 A
15–30 A
—
QO (B) EPD
—
—
15–50 A
—
15–50 A
QO (B) EPE
—
QO (B)
15–70 A
15–125 A 15–100 A
QO (B) GFI
15–30 A
15–60 A
—
QO (B) EPD
15–30 A
15–60 A
15–50 A
QO (B) EPE
—
—
15–50 A
400 A max. Fusibles classe J ou T6
QO (B) VH
—
—
15–30 A
400 A max. Fusibles classe J
QO (B) VH
—
—
15–30 A
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B) VH
—
—
15–150 A
QOB VH 1φ, 2F uniquement
—
150 A
—
QO (B)
—
—
15–100 A
QO (B) VH
—
—
65 000 400 A max. Fusibles classe T6
100 000
15–70 A
200 A max. Fusibles classe T3
15–30 A Page suivante
37
FRANÇAIS
100 000
QO (B) QO (B) VH
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
80043-712-06 Rév. 02 11/2016
Tableau 2 : Val. nom. de disjoncteurs raccordés en série (RMS sym.) (suite) Désignation du catalogue des Disjoncteurs Courant Tension ca nominal principaux intégrés ou disjoncteurs de dérivation de la marque Square D et gammes d'intensité de court- à distance et fusibles max. du admissibles 3, 4, 5, 6 principaux à distance circuit système 1, 2 de la marque Square D max. Type 1 pôle 2 pôles 3 pôles
240 3P/3F ou 240 1P/2F (2 pôles uniquement)
200 A max. Fusibles classe J ou T6 200 000
400 A max. Fusibles classe T3
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
QO (B)
—
—
15–100 A
QO (B) EPD
—
—
15–50 A
QO (B) EPE
—
—
15–50 A
FRANÇAIS
1
Pour les disjoncteurs montrés d’une tension nominale inférieure à cette tension maximale, le courant nominal de court-circuit indiqué s’applique également, mais à la tension nominale du disjoncteur.
2
Les essais de courts-circuits sont effectués de 100 à 105 % de la tension nominale maximale du panneau de commutation combiné I-Line.
3
Les suffixes HID, SWD et SWN peuvent être aussi appliqués aux disjoncteurs de dérivation qui conviennent et indiqués ci-dessus. Le suffixe SWN ne peut pas être appliqué en combinaison avec les disjoncteurs principaux LC.
4
Là où les disjoncteurs QO (B) sont indiqués ci-dessus, les disjoncteurs QO (B) H, QO (B) VH et QH (B) peuvent également être utilisés.
5
Là où les disjoncteurs QO (B) GFI sont indiqués ci-dessus, les disjoncteurs QO (B) EPD ou QO (B) EPE peuvent également être utilisés.
6
Là où les disjoncteurs QO (B) AFI sont indiqués ci-dessus, les disjoncteurs QO (B) CAFI peuvent également être utilisés.
7
Les disjoncteurs bipolaires CAFI sont seulement de 120/240 Vca et ne peuvent être utilisés que sur des systèmes à 3 fils, monophasés, de 120/240 Vca.
8
Pour obtenir une coordination sélective, la valeur nominale du disjoncteur principal DJ doit être au moins deux fois plus importante que l'intensité nominale de tout disjoncteur de dérivation.
38
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
Tableau 3 : Sélectivité de disjoncteur critique pour panneau NQ
Pleine valeur nominale et sélectif jusqu'à 10 kA à 208 Y/120 Vca ou à 240/120 Vca Valeur nominale en série et sélectif jusqu'à 12kA à 208 Y/120 Vca ou à 240/120 Vca Valeur nominale en série et sélectif jusqu'à 15kA à 208 Y/120 Vca ou à 240/120 Vca
Disjoncteurs principaux intégrés ou à distance
Disjoncteurs de dérivation Type1
Unipolaire Bipolaire Tripolaire
QO(B) J-W, 250 A
QO(B)-H
L-W, 250 A
QO(B)-VH
10–70
10–125
10–125
10–70
10–125
10–60
10–60
10–60
10–30
10–30
10–30
—
10–60
10–60
10–60
15–70
15–150
15–150
QH QO(B) J-W, 250 A
QO(B)-H QO(B)-VH QH QO(B)
J-W, 250 A
QO(B)-H QO(B)-VH
FRANÇAIS
SCCR maximum (RMS symétriques)
QH QO(B) J-W, 250 A
Valeur nominale en série et sélectif jusqu'à 18kA à 208 Y/120 Vca ou à 240/120 Vca
QO(B)-H QO(B)-VH QH QO(B)
L-W, 250 A
QO(B)-H QO(B)-VH QH
Valeur nominale en série et sélectif jusqu'à 30kA à 208 Y/120 Vca ou à 240/120 Vca 1
QO(B) L-W, 400 A
QO(B)-H
L-W, 600 A
QO(B)-VH QH
Y compris les disjoncteurs AFI, CAFI, EPD et GFI.
39
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 1 : Spécifications
80043-712-06 Rév. 02 11/2016
Tableau 4 : Courant nominal de court-circuit1 pour intérieurs à cosses principales avec cosses de traversée ou de sous-alimentation Tension ca Courant nominal maximale du système maximal 100
Circuits d'artère
Application
18, 30 30, 42, 54, 72, 84, 96
225
30, 42, 54, 72, 84 240
96 400
SFL and FTL
—
SFL
6 pouces (152.4 mm)
42 30, 54, 72, 84, 96
— FTL
SFL
Courant nominal de court-circuit max.3
10,000
6 pouces (152.4 mm) —
25,000
—
10,000
FRANÇAIS
30, 84
—
25,000
96
—
10,000
6 pouces (152.4 mm)
25,000
12 pouces (304.8 mm)
10,000
FTL
42, 54, 72 600
Addition2
30, 42, 54, 72, 84 96
FTL
1
Ces valeurs nominales concernent les intérieurs à cosses principales, munis de cosses de sous alimentation ou de traversée, où le dispositif alimentant l'intérieur est inconnu ou autre qu'un dispositif de marque Square D. L'utilisation d'un disjoncteur principal de la marque Square D en amont de ces cosses aboutira à une valeur nominale égale à la valeur nominale du disjoncteur. Les essais de courts-circuits sont effectués de 100 à 105 % de la tension nominale maximale du panneau de distribution.
2
Addition est la longueur supplémentaire du coffret.
3
Ampères rms symétriques, pour trois cycles.
Marquage CE
40
•
Les intérieurs avec la marque CE sont conformes aux normes IEC 61439-1 et IEC 61439-2.
•
Les intérieurs à cosses principales avec la marque CE ont été vérifiés pour supporter 10 000 A RMS symétriques pendant 30 cycles.
•
Les intérieurs avec la marque CE ne sont approuvés que pour une utilisation avec les disjoncteurs de dérivation QOXD ou QOBXD qui comportent la marque CE.
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 2 : Accessoires
Annexe 2 : Accessoires Un assortiment d’accessoires pouvant être installés sur place est disponible pour les panneaux de distribution NQ :
• •
Kits de barre de m.à.l.t. de l’appareil
•
Kits de cosses de sous-alimentation pour les panneaux de distribution de 100 à 400 A
•
Kit de cosse principale
Kits de cosses surdimensionnées pour les panneaux de distribution de 100 à 250 A
— Kits de cosses mécaniques — Aluminum — Kits de cosses mécaniques — Cuivre — Kits de cosses à compression Versa-Crimp® — Aluminum FRANÇAIS
— Kits de cosses à compression Versa-Crimp — Cuivre
Kits de barre de m.à.l.t. de l’appareil Les kits de barre de m.à.l.t. de l’appareil, convenant à du fil de cuivre ou d’aluminium, répondent aux besoins de m.à.l.t. des panneaux de distribution NQ ou des centres de distribution QONQ. Tableau 5 : Spécifications des kits de barre de m.à.l.t. de l’appareil Panneaux de distribution Circuit d'artère 1–42 54–84
Utiliser le numéro de catalogue du kit de barre de m.à.l.t.
Valeur nominale Aluminium1 du secteur 600 A maximum
Cuivre2
(1) PK27GTA
(1) PK27GTACU
(2) PK27GTA
(2) PK27GTACU
1
Barres en aluminium convenant à des conducteurs en cuivre ou aluminium de 60 °C ou 75 °C.
2
Barres en cuivre convenant à des conducteurs en cuivre de 60 °C ou 75 °C.
REMARQUE : Les emplacements de montage d’une barre de m.à.l.t. sont identifiés par le symbole de terre estampé sur la paroi arrière du coffret.
41
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 2 : Accessoires
80043-712-06 Rév. 02 11/2016
Kits de cosses surdimensionnées pour les panneaux de distribution de 100 à 250 A Les kits de cosses surdimensionnées sont disponibles pour les applications dans lesquelles des conducteurs de terminaison d’un calibre de 3 AWG ou plus grand sont requis pour le neutre. Tableau 6 : Spécifications du kit de cosses surdimensionnées pour les panneaux de distribution de 100 à 250 A
FRANÇAIS
Valeur nominale du disjoncteur
Nº de catalogue du kit
70 A
QO70AN
80 à 125 A
Q1100AN
(1) 4–1/0 Al/Cu (1) 42,4–53,5 mm2
125 à 150 A
Q1150AN
(1) 1–4/0 Al/Cu (1) 42,4–107 mm2
Calibre des fils (1) 10–2 Al (1) 5,76–33,6 mm2 (1)14–4 Cu (1) 2,08–21,1 mm2
Kits de cosses de sous-alimentation pour les panneaux de distribution de 100 à 400 A Des cosses principales de sous-alimentation sont disponibles pour les applications de 100, 225 ou 400 A. Tableau 7 : Spécifications du kit de cosses de sousalimentation pour les panneaux de distribution de 100 à 400 A Intensité principale
Nº de catalogue du kit
Nombre max. de circuits
100
NQSFL1
18, 30
225
NQSFL2
301, 421, 541, 721, 841
400
NQSFL4
30, 42, 54, 72, 84
1
42
Ces panneaux exigent 152,4 mm (6 pouces) supplémentaires pour le coffret et la garniture, afin d’avoir un espace de courbure des fils appropriés.
80043-712-06 Rév. 02 11/2016
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 2 : Accessoires
Kit de cosse principale Tableau 8 : Kits de cosses mécaniques — Aluminum Intensité du panneau de distribution
Nº de catalogue du kit
100
Standard
225
Standard
400
Standard
Calibre des fils No 6–2/0 AWG 13,3–67,43 mm2 No 6–350 kcmil 13,3–177,3 mm2 (1) 1/0–750 kcmil (2) 1/0–350 kcmil (1) 53,48–380 mm2 (2) 53,48–177,3 mm2 (2) 1/0–750 kcmil (2) 53,48–380 mm2 (3) #6–250 kcmil (3) 13,3–127 mm2
Standard 600 NQALM6A
Tableau 9 : Kits de cosses mécaniques — Cuivre Nº de catalogue du kit
100
NQCUM1
225
NQCUM2
400
NQCUM4
600
NQCUM6
Calibre des fils
FRANÇAIS
Intensité du panneau de distribution
No 6–2/0 AWG 13,3–67,43 mm2 No 6 à 250 kcmil 13,3–127 mm2 (1) 1/0–750 kcmil (2) 1/0–350 kcmil (1) 53,48–380 mm2 (2) 53,48–177,3 mm2
Tableau 10 : Kits de cosses à compression Versa-Crimp® — Aluminum Intensité du panneau de distribution Nº de catalogue du kit Calibre des fils 100
NQALV1
225
NQALV2
400 600
NQALV4 NQALV6
Outil de sertissage
No 8–1/0 AWG 8,36–53,48 mm2 VC6 (tous) No 4 à 300 kcmil 21,15–152 mm2 (2) 2/0–500 kcmil VC6-3, (2) 67,43–253,4 mm2 VC6-FT
Tableau 11 : Kits de cosses à compression Versa-Crimp — Cuivre Intensité du panneau de distribution Nº de catalogue du kit Calibre des fils 100
NQCUV1
No 6–1/0 AWG 13,30–53,48 mm2
225
NQCUV2
2/0 à 300 kcmil 67,43–152 mm2
400
NQCUV4
400–750 kcmil 202,7–380 mm2
600
NQCUV6
(2) 250–500 kcmil (2) 126,7–253,4 mm2
Outil de sertissage VC6 (tous) VC7 (tous) VC6-3, VC7, VC6-FT, VC7-FT VC6-FT, VC7-FT, VC8 VC6-3, VC7, VC6-FT, VC7-FT
43
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Annexe 2 : Accessoires
FRANÇAIS 44
80043-712-06 Rév. 02 11/2016
FRANÇAIS
Pour panneaux de distribution NQ/NQM et centres de distribution QONQ Directives d’utilisation
FRANÇAIS Seul un personnel qualifié doit effectuer l’installation, l’utilisation, l’entretien et la maintenance du matériel électrique. Schneider Electric n’assume aucune responsabilité des conséquences éventuelles découlant de l’utilisation de cette documentation.
Schneider Electric Canada 5985 McLaughlin Road Mississauga, ON L5R 1B8 Canada 1-800-565-6699 www.schneider-electric.ca
© 2007–2015 Schneider Electric Tous droits reserves Schneider Electric et Square D sont marques commerciales de Schneider Electric Industries SAS ou de ses compagnies affiliées. Toutes les autres marques commerciales utilisées dans ce document sont la propriété de leurs propriétaires respectifs. 80043-712-06 Rev. 02, 11/2016 Remplace 80043-712-06 Rev. 02, 06/2015
NQ/NQM Panelboards and QONQ Load Centers Para los tableros de alumbrado NQ/NQM y centros de carga QONQ Pour panneaux de distribution NQ/NQM et centres de distribution QONQ
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
Solamente el personal especializado deberá instalar, hacer funcionar y prestar servicios de mantenimiento al equipo eléctrico. Schneider Electric no asume responsabilidad alguna por las consecuencias emergentes de la utilización de este material.
Seul un personnel qualifié doit effectuer l’installation, l’utilisation, l’entretien et la maintenance du matériel électrique. Schneider Electric n’assume aucune responsabilité des conséquences éventuelles découlant de l’utilisation de cette documentation.
© 2007–2015 Schneider Electric All Rights Reserved
© 2007–2015 Schneider Electric Reservados todos los derechos
© 2007–2015 Schneider Electric Tous droits reserves
Schneider Electric and Square D are trademarks owned by Schneider Electric Industries SAS or its affiliated companies. All other trademarks are the property of their respective owners.
Schneider Electric y Square D son marcas comerciales de Schneider Electric Industries SAS o sus compañías afiliadas. Todas las otras marcas comerciales son propiedad de sus respectivos propietarios.
Schneider Electric et Square D sont marques commerciales de Schneider Electric Industries SAS ou de ses compagnies affiliées. Toutes les autres marques commerciales utilisées dans ce document sont la propriété de leurs propriétaires respectifs.
Schneider Electric USA, Inc. 1415 S. Roselle Road Palatine, IL 60067 USA 1-888-SquareD www.us.SquareD.com
Importado en México por: Schneider Electric, S.A. de C.V. Calz. J. Rojo Gómez 1121-A Col. Gpe. del Moral 09300 México, D.F. Tel. 55-5804-5000 www.schneider-electric.com.mx
Schneider Electric Canada, Inc. 5985 McLaughlin Road Mississauga, ON L5R 1B8 Canada Tel:1-800-565-6699 www.schneider-electric.ca
80043-712-06 Rev. 02 11/2016 Replaces 80043-712-06 Rev. 02, 06/2016
80043-712-06 Rev. 02 11/2016 Reemplaza 80043-712-06 Rev. 02, 06/2016
80043-712-06 Rev. 02 11/2016 Remplace 80043-712-06 Rev. 02, 06/2016
Addendum
Anexo
80043-842-01 08/2018
Annexe
California Proposition 65 Warning— Nickel Compounds and Bisphenol A (BPA) Advertencia de la Proposición 65 de California— compuestos de níquel y Bisfenol A (BPA) Avertissement concernant la Proposition 65 de Californie—composés de nickel et Bisphénol A (BPA) WARNING: This product can expose you to chemicals including Nickel compounds, which are known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings. ca.gov.
All trademarks are the property of Schneider Electric SE, its subsidiaries, and affiliated companies.
ADVERTENCIA: Este producto puede exponerle a químicos incluyendo compuestos de níquel, que son conocidos por el Estado de California como causantes de cáncer, y Bisfenol A (BPA), que es conocido por el Estado de California como causante de defectos de nacimiento u otros daños reproductivos. Para mayor información, visite www.P65Warnings.ca. gov.
Todas las marcas comerciales son propiedad de Schneider Electric SE, sus filiales y compañías afiliadas.
AVERTISSEMENT: Ce produit peut vous exposer à des agents chimiques, y compris composés de nickel, identifiés par l'État de Californie comme pouvant causer le cancer, et Bisphénol A (BPA) reconnus par l'État de Californie comme pouvant causer des malformations congénitales ou autres troubles de l'appareil reproducteur. Pour de plus amples informations, prière de consulter www.P65Warnings.ca.gov.
Toutes les marques commerciales sont la propriété de Schneider Electric SE, ses filiales et compagnies affiliées.
Importado en México por:
Schneider Electric USA, Inc.
Schneider Electric México, S.A. de C.V.
Schneider Electric Canada, Inc.
800 Federal Street Andover, MA 01810 USA 888-778-2733 www.schneider-electric.us
Av. Ejercito Nacional No. 904 Col. Palmas, Polanco 11560 México, D.F. 55-5804-5000 www.schneider-electric.com.mx
5985 McLaughlin Road Mississauga, ON L5R 1B8 Canada 800-565-6699 www.schneider-electric.ca
© 2018 Schneider Electric All Rights Reserved / Reservados todos los derechos / Tous droits réservés