To install to existing Vaporgard mounts:

Vaporgard™ LED Luminaires V2L Series

IF 1611

Installation & Maintenance Information

Attach the LED housing. a.

Hang the assembly on the hinge of the adapter module (see Figure 3).

1.

Loosen the mounting screws on the existing mount. Remove old luminaire, including the VHF adapter section, leaving mount in place. Keep the two luminaire mounting screws in place in the existing mount.

b.

Pull wiring into cover.

c.

Connect cover ground lead with fork terminal to ground screw on LED housing. Tighten ground screw (see Figure 4).

2.

Clean all debris from the luminaire mounting surface using mild soap or a liquid cleaner such as Collinite NCF or Duco #7.

d.

Connect supply wires to the LED driver input leads per the appropriate wiring diagram, using methods that comply with all applicable codes. Tighten all electrical connections.

3.

Slip the keyhole slots of the VLHR adapter cover over the screws on the mount. Twist the VLHR counterclockwise to lock it in place.

e.

4.

Snug the two screws, and then, in the same order, torque each screw to 20 lb.-in. (2.3 N-m).

Close LED housing onto adapter cover, ensuring that wires are not caught between the cover and LED housing. Tighten three (3) screws provided using a 3/16 inch (4.7 mm) hex allen wrench (see Figure 5). Torque to 30 lb.-in. (3.4 N-m).

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

APPLICATION Vaporgard™ LED Series Luminaires are suitable for use in the following hazardous (classified) areas as defined by the National Electrical Code (NEC®): NEC/CEC Refer to the luminaire nameplate for specific classification information, • Class I, Division 2, Groups A, B, C, D maximum ambient temperature suitability, and corresponding operating • Wet location, NEMA 3, NEMA 4, Marine temperature (T-Code). UL Standards Vaporgard Series Luminaire construction is designed for use indoors and • UL 844 Hazardous (classified) outdoors in marine and wet locations, where moisture, dirt, corrosion, • UL1598 Luminaires, UL1598A Marine vibration, and rough usage may be present. CSA Standards Vaporgard Series may be wired to 120 - 240 Volts AC 50/60 Hz, or 277 Volts • CSA C22.2 No. 137 50/60 Hz, or 12-24 Volts DC.

5.

NOTE: Vaporgard LED can be mounted to existing surface-mounted ceiling junction box VXF or VXFT, or to wall mount arm VXHT only.

Electrical ratings:

LED Housing Ground Screw

AC:

DC:

• 120-240/277 VAC, 50/60 Hz

• 12-24 VDC

• 0.2-0.4/0.1 Amps

• 1.2-1.7 Amps