Documento no encontrado! Por favor, inténtelo de nuevo

Humidity and Temperature Transmitter for HVAC ... - Sensovant

Connection diagram. EE160-HT6xAPAB-Tx003M. Model: humidity + temperature transmitter. Analog output: 4-20mA. Passive T-Sensor: Pt 100 DIN A. Housing:.
549KB Größe 10 Downloads 220 vistas
T: (+34) 968 162 005 www.sensovant.com [email protected]

EE160

Humidity and Temperature Transmitter for HVAC Applications

Specially designed for HVAC, the EE160 sensor by E+E Elektronik is a costeffective, highly accurate and reliable solution for measuring relative air humidity and temperature. The enclosure minimizes installation costs and provides outstanding protection against contamination and condensation, thus ensuring flawless operation. The EE160 employs the new humidity/temperature E+E sensor element HCT01 with excellent long term stability and resistance against pollutants. In combination with a long calibration experience, the EE160 provides a measurement accuracy of ±2.5%RH and is available for wall or duct-mounted with current, voltage BACnet MS/TP or Modbus RTU output.

EE160

A configurator makes it possible to freely select the scaling of the temperature output and configure the Modbus parameters. The configurator software, which is free of charge, allows additionally for an on-site adjustment of the humidity and temperature.

Appropriate for US mounting requirements » Knockout for ½” conduit fitting

External mounting holes » Mounting with closed cover » Electronics protected against construction site pollution » Easy and fast mounting

Electronics on the underside of the PCB » Optimum protection against mechanical damage during installation

Bayonet Screws

IP65 / NEMA 4 Enclosure

» Open/closed with a ¼ rotation

Cast Electronics » Mechanical protection » Condensation-resistant

E+E Humidity sensor HCT01 » Long-term stability » Protected RH sensor surface » Protected solder pads » Tested according to automotive standard AEC-Q200 BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to the requirements of ASHRAE Standard 135 is the responsibility of BACnet International (BI). BTL is a registered trademark of BI.

10

v2.0 / Modification rights reserved

EE160

T: (+34) 968 162 005 www.sensovant.com [email protected]

Technical data Measured values

Relative Humidity Sensor Working range Accuracy at 20°C Temperature dependency Temperature Sensor T-Accuracy at 20°C

E+E Sensor HCT01-00D 10...95% RH ±2.5% RH typ. ±0.03% RH/°C Pt1000 (tolerance class B, DIN EN 60751) ±0.3°C

Outputs

Analog output (RH: 0...100%; T: see ordering guide) Digital output Passiver T-sensor 4-wire

General

Power supply for 0 - 10 V / RS485 for 4 - 20 mA Current consumption Analog Digital Connection Housing material Protection class Cable gland Sensor protection Electromagnetic compatibility Temperature ranges

0-10 V -1 mA < I < 1 mA or 4-20 mA (two-wire) R < 500 Ohm RS485 (BACnet MS/TP or Modbus RTU) max. 32 EE160 in one bus L

L

see ordering guide

15 - 35V DC or 24V AC ±20% 10V + R x 20 mA < U < 35V DC L

V

with DC power supplytyp. 5mA with AC power supply typ. 13mAeff with DC power supplytyp. 15mA with AC power supplytyp. 25mAeff Screw terminals, max. 1.5 mm2 Polycarbonate, UL94V-0 approved IP65 / NEMA 4 M16 x 1.5 membrane filter EN61326-1 EN61326-2-3 Operating temperature: -40...60°C Storage temperature: -20...60°C

(-40...140°F) ( -4...140°F)

Dimensions (mm) 90 ±0.3mm 3.54 ±0.11“ 90 ±0.3mm 3.54 ±0.11“

Conduit gland Ø > 13mm Ø > 0.51“

46m 1.8 m 1“

m 101m 3.98“

80.6mm 3.17“

~20 5 ~8. mm 07“

5mm 0.2“

GASKET

60 ±0.3mm 2.36 ±0.11“ ~55mm ~2.16“

Ø > 16mm Ø > 0.63“

Ø 12mm Ø 0.47“

Type A EE160

Cable gland 19mm 0.75“

v2.0 / Modification rights reserved

6mm 0.24“

Type B

Recommended mounting screws: ST4.2x50 DIN7981C

11

T: (+34) 968 162 005 www.sensovant.com [email protected]

Connection diagram 8 7 6 5

EE160-HT3xxx

EE160-HT6xxx

8 7 6 5

EE160-HTx3xx

T-passive connection for HT3xxx/HT6xxx 8 7 6 5

Ordering Guide

Hardware configuration MODEL

humidity + temperature

ANALOG1)

(HT) 0-10V 4-20mA none

DIGITAL1)

(3) RS485 (6) none (x)

PASSIVE T-SENSOR2)

(3) Pt 100 DIN A (x) Pt 1000 DIN A NTC 10k Ni1000, TK6180 none

HOUSING

TYPE

FILTER

(A) polycarbonate (P) wall mount (C) duct mount (E) (J) (x)

(A) membrane filter (B) (B)

EE160Analogue outputs setup OUTPUT SCALING

(Tx)

temperature

SCALING3) -20...80 -40...60 -10...50 0...50

°C

UNIT

°F

(024) 32...122 (002) -40...140 (003) 0...140 (004) 20...120

(M) (N)

metric (076) non-metric (083) (085) (015)

Digital output setup PROTOCOL Modbus RTU4) BACnet MS/TP5)

BAUDRATE (1) 9600 (3) 19200 38400 576006) 768006) 1152006)

1) A combination of analog and digital version is not possible 2) Analogue version only 3) Other scaling upon request

PARITY

STOPBITS

(A) odd (B) even (C) no parity (D) (E) (F)

(O) 1 stopbit (E) 2 stopbit (N)

UNIT (1) metric (2) non-metric

(M) (N)

4) Modbus Map and setup instructions: See User Guide and Modbus Application Note at www.epluse.com/EE160 5) Product Implementation conformance Statement (PICS) availbale at www.epluse.com/EE160 6) Only for BACnet

Order example Analog output EE160-HT6xAPAB-Tx003M Model: Analog output: Passive T-Sensor: Housing: Type: Filter:

humidity + temperature transmitter 4-20mA Pt 100 DIN A polycarbonate wall mounting membrane filter

Digital output EE160-HTx3xPBB-1AE1N Model: Digital output: Housing: Type: Filter:

humidity + temperature transmitter RS485 polycarbonat duct mounting membrane filter

Output scaling: Scaling: Unit:

temperature -10...50° metric

Protocol: Baudrate: Parity: Stopbits: Unit:

Modbus 9600 even 1 non-metric

12

v2.0 / Modification rights reserved

EE160

T: (+34) 968 162 005 www.sensovant.com [email protected]

Accessories Product configuration adapter Product configuration software Power supply adapter

see data sheet EE-PCA EE-PCS (free download: www.epluse.com/EE160) V03 (see data sheet Accessories)

Scope of supply EE160 Wall mount (Type A)

Model

EE160 Duct mount (Type B)

Additionally for all EE160 with RS485 interface

EE160 Transmitter according ordering guide Cable gland Mounting kit Mounting flange Inspection certificate according to DIN EN10204 - 3.1 Quick Guide EE160 RS485 Setup

EE160 EE160

v2.0/ /Modification Modificationrights rightsreserved reserved v2.0

13 13