(+34) 968 162 005 www.sensovant.com
[email protected]
EE046
Condensation Monitor
EE046 condensation monitor helps prevent condensation on chilled beams and other critical cold spots and is appropriate for mounting onto plane surfaces and on pipes with max. 50 mm (2”) diameter. It features the well-proven E+E HC105 SMD humidity sensor. Condensation on a surface occurs when the relative humidity (RH) of the air close to the surface reaches 100 % RH. Because of very good thermal coupling with the surface, EE046 measures directly the RH of the air at surface temperature.
EE046
The relay output gives an early warning when approaching condensing conditions, before condensation actually happens. It indicates also a power supply failure or a broken cable. A status LED indicates normal operation, alarm or power supply failure. The E+E proprietary coating protects the humidity sensor against dust and dirt.
Typical Applications
Features
early detection of condensation danger chilled beams switching cabinets climate control
fast response time dust protection compact design and easy mounting LED status indication
Technical Data Humidity sensor Working range Threshold at 20 °C Hysteresis
(68°F),
24 V AC/DC
Hysteresis 5 % RH
Response time at change of the surface temperature Response time at change of the relative humidity Electrical output Switching capability Supply voltage (Class III) Current consumption Relay status indication Electrical connection Protection sensor / electronics Housing protection class Housing material Electromagnetic compatibility Temperature range Weight 30
E+E HC105 10...100 % RH 90±3 % RH
operation storage
85±3 % RH
t90 < 3 min.
90±3 % RH
t90 < 25 sec. potential free relay with changeover contact max. 24 V AC/DC, 1A 24 V AC/DC ±20 % < 6 mA for 24 V DC supply < 10 mA for 24 V AC supply LED, red 5-pole push-in terminal, max. 1.5 mm2 (AWG 16) E+E proprietary coating / varnish IP40 Polycarbonate, UL94-V2 approved EN 61326-1 EN 61326-2-3 industrial environment 0...50 °C (32...122 °F) -20...70 °C ( -4...158 °F) approx. 60 g v1.0 / Modification rights reserved
EE046
(+34) 968 162 005 www.sensovant.com
[email protected]
Dimensions (mm/inch)
Installation
max. Ø 50 (2“)
Pipe mount
m ax
.Ø
50
(2
“)
thermal conductive film
Wall mount
22 (0.87“) Ø4.5 (Ø 0.18“)
23 (0.9“)
status LED
thermal conductive film
63.5 (2.5“)
33.5 (1.32“)
43 (1.69“) 53 (2.09“)
Connection Diagram / Status Indication power supply 24 V AC/DC ±20 %
+ ~
V+
-
GND
~
*
Relay Function RH (%)
WET
90
COM
85
~ ~
DRY
* Relay status for power on and RH < 90%. The relay falls to “WET” for RH > 90% or power off.
LED ON: LED flashes: LED OFF:
no condensation danger condensation danger power supply off / failure
0
V+ (V)
24
0
Relays
WET
DRY
Ordering Guide Condensation Monitor EE046 EE046
v1.0 / Modification rights reserved
EE046 31